18.3
Error Code Table
Diagnosis
Abnormality /
display
Protection control
H
0
0
N
o
m
e
m
o
y r
H11
Indoor/outdoor
abnormal
communication
H12
Indoor unit capacity
unmatched
H14
Indoor intake air
temperature sensor
abnormality
H15
Compressor
temperature sensor
abnormality
H16
Outdoor current
transformer (CT)
abnormality
H19
Indoor fan motor
merchanism lock
H23
Indoor heat exchanger
temperature sensor
abnormality
H24
Indoor heat exchanger
temperature sensor 2
abnormality
H27
Outdoor air temperature
sensor abnormality
H28
Outdoor heat exchanger
temperature sensor 1
abnormality
H30
Outdoor discharge pipe
temperature sensor
abnormality
H32
Outdoor heat exchanger
temperature sensor 2
abnormality
H33
Indoor / outdoor
misconnection
abnormality
H36
Outdoor gas pipe
temperature sensor
abnormality
H37
Outdoor liquid pipe
temperature sensor
abnormality
H38
Indoor/Outdoor
mismatch (brand code)
H39
Abnormal indoor
operating unit or
standby units
H41
Abnormal wiring or
piping connection
Abnormality
Judgement
f o
a f
u l i
e r
—
After operation for
1 minute
90s after power
supply
Continuous for 5s
Continuous for 5s
—
Continuous
happen for 7 times
Continuous for 5s
Continuous for 5s
Continuous for 5s
Continuous for 5s
Continuous for 5s
Continuous for 5s
—
Continuous for 5s Heating protection
Continuous for 5s Cooling protection
—
3 times happen
within 40 minutes
—
Protection
Problem
operation
N
r o
m
l a
o
p
r e
t a
o i
n
Indoor fan only
Indoor/outdoor
operation can
communication not establish
start by entering
into force cooling
operation
—
Total indoor capability more
than maximum limit or less
than minimum limit, or
number of indoor unit less
than two.
—
Indoor intake air temperature
sensor open or short circuit
—
Compressor temperature
sensor open or short circuit
—
Current transformer faulty or
compressor faulty
—
Indoor fan motor lock or
feedback abnormal
—
Indoor heat exchanger
temperature sensor open or
short circuit
—
Indoor heat exchanger
temperature sensor 2 open
or short circuit
—
Outdoor air temperature
sensor open or short circuit
—
Outdoor heat exchanger
temperature sensor 1 open
or short circuit
—
Outdoor discharge pipe
temperature sensor open or
short circuit
—
Outdoor heat exchanger
temperature sensor 2 open
or short circuit
—
Indoor and outdoor rated
voltage different
Outdoor gas pipe
operation only
temperature sensor open or
short circuit
Outdoor liquid pipe
operation only
temperature sensor open or
short circuit
—
Brand code not match
—
Wrong wiring and connecting
pipe, expansion valve
abnormality, indoor heat
exchanger sensor open
circuit
—
Wrong wiring and
connecting pipe, expansion
valve abnormality
76
Check location
—
• Indoor/outdoor wire terminal
• Indoor/outdoor PCB
• Indoor/outdoor connection wire
• Indoor/outdoor connection wire
• Indoor/outdoor PCB
• Specification and combination
table in catalogue
• Indoor intake air temperature
sensor lead wire and connector
• Compressor temperature sensor
lead wire and connector
• Outdoor PCB faulty or
compressor faulty
• Fan motor lead wire and
connector
• Fan motor lock or block
• Indoor heat exchanger
temperature sensor lead wire and
connector
• Indoor heat exchanger
temperature sensor 2 lead wire
and connector
• Outdoor air temperature sensor
lead wire and connector
• Outdoor heat exchanger
temperature sensor 1 lead wire
and connector
• Outdoor discharge pipe
temperature sensor lead wire and
connector
• Outdoor heat exchanger
temperature sensor 2 lead wire
and connector
• Indoor and outdoor units check
• Outdoor gas pipe temperature
sensor lead wire and connector
• Outdoor liquid pipe temperature
sensor lead wire and connector
• Check indoor unit and outdoor
unit.
• Check the indoor/outdoor
connection wire and connection
pipe.
• Indoor heat exchanger sensor
lead wire and connector.
• Expansion valve and lead wire
and connector system.
• Check indoor/outdoor
connection wire and connection
pipe
• Expansion valve and lead wire
and connector
—