15.1.5
Compressor Overheating Prevention Control
Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The
changes of frequency are as below.
If compressor discharge temperature exceeds 224.6°F, compressor will be stopped, occurs 4 times per
20 minutes, timer LED will be blinking. ("F97" is indicated.)
15.1.6
Low Pressure Prevention Control (Gas Leakage Detection)
Control start conditions
For 5 minutes, the compressor continuously operates and outdoor total current is between 0.64A and 0.85A.
o
During Cooling and Soft Dry operations:
o
Indoor suction temperature - indoor piping temperature is below 7.2.°F.
During Heating operations:
o
Indoor piping temperature - indoor suction is under 9°F.
Control contents
Compressor stops (and restart after 3 minutes).
o
If the conditions above happen 2 times within 20 minutes, the unit will:
o
Stop operation
Timer LED blinks and "F91" indicated.
15.1.7
Low Frequency Protection Control 1
When the compressor operates at frequency lower than 24Hz continued for 240 minutes, the operation frequency
will be changed to 25Hz for 2 minutes.
15.1.8
Low Frequency Protection Control 2
When all below conditions comply, minimum limit of compressor will be set.
Indoor intake air (°F)
Outdoor air (°F)
Indoor heat exchanger (°F)
o
224.6
F
Compressor Frequency
o
217.4
F
Compressor Frequency
o
212
F
Comp. Discharge temperature
Temperature, T, for:
Compressor = OFF
o
197.6
F
Reduce
o
195.8
F
Maintain
o
194
F
Free
Cooling / Soft Dry
T < 57.2 or T ≥ 86
T < 55.4 or T ≥ 100.4
T < 57.2 or T ≥ 82.4
T < 86
62
Heating
-
T ≥ 32