Single Refrigerant System With Two Or More Lossnay Units - Mitsubishi Electric PURY-P200YLM-A(1) Service Handbook

Table of Contents

Advertisement

[2-7 Example System with an MA Remote Controller ]
2-7-2

Single Refrigerant System with Two or More LOSSNAY Units

(1) Sample control wiring
Leave the male
connector on
CN41 as it is.
SW5-1 OFF
OS
52
TB3
TB7
M1 M2
M1 M2
S
(2) Cautions
1)
ME remote controller and MA remote controller cannot both be
connected to the same group of indoor units.
2)
No more than 2 MA remote controllers can be connected to a
group of indoor units.
3)
When the number of the connected indoor units is as shown in
the table below, one or more transmission boosters (sold sepa-
rately) are required.
To connect two transmission boosters, connect them in parallel.
(Observe the maximum number of connectable indoor units that
are listed in the specifications for each outdoor unit.)
When the P200 and P250 models are
not included in the connected indoor
units
When the P200 and P250 models are
included in the connected indoor
units
The table above shows the number of transmission boost-
HWE1314A
L1
L2
Leave the male
connector on
CN41 as it is.
SW5-1 OFF
OC
BC
51
53
TB3
TB02
TB7
M1 M2
M1 M2
S
M1 M2
S
M1 M2
S
TB02
57
BS
* If the BC address overlaps any of the addresses that are assigned to either the OC, OS, or BS, use a different, unused address.
OC, OS, and BS addresses (lowest indoor unit address in the group plus +50) have higher priority than the BS address.
Number of transmission booster
(sold separately) required
1 unit
2 units
27 - 50 units
21 - 39 units
40 - 50 units
L3
L4
Group
IC
01
TB5
TB15
M1M2
S
1 2
A1 B2
MA
L12
Group
IC
03
TB5
TB15
M1M2
S
1 2
A1 B2
MA
IC
07
TB5
TB15
M1M2
S
1 2
A1 B2
MA
ers that is required by the system with three BC controllers.
For each BC controller that is subtracted from the above-
mentioned system, two additional indoor units can be con-
nected.
Refer to the DATABOOK for further information about how
many booster units are required for a given system.
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Same as 2-7-1
2) Transmission line for centralized control
No connection is required.
3) MA remote controller wiring
Same as 2-7-1
-
- 36 -
Interlock operation with the ventilation unit
L5
Group
LC
IC
02
05
TB5
TB15
TB5
M1M2
S
1 2
M1M2
S
A1 B2
MA
L13
LC
IC
04
06
TB5
TB15
TB5
M1M2
M1M2
S
1 2
S
m3
IC
08
TB5
TB15
M1M2
S
1 2
A1 B2
MA
GB