Error Code Definitions And Solutions: Codes [1000 - 1999]; Error Code [1102] - Mitsubishi Electric PURY-P200YLM-A(1) Service Handbook

Table of Contents

Advertisement

[7-3 Error Code Definitions and Solutions: Codes [1000 - 1999] ]

7-3

Error Code Definitions and Solutions: Codes [1000 - 1999]

7-3-1

Error Code [1102]

1. Error code definition
Discharge temperature fault
2. Error definition and error detection method
1) If the discharge temperature of 120 °C [248°F] or more is detected during the above operation (the first detection), the outdoor
unit stops once, turns to anti-restart mode for 3 minutes, and restarts after 3 minutes automatically.
2) If the discharge temperature of 120° C [248°F] or more is detected again (the second detection) within 30 minutes after the
second stop of the outdoor unit described above, the mode will be changed to 3 - minute restart mode, then the outdoor unit
will restart in 3 minutes.
3) If the discharge temperature of 120°C [248°F] or more is detected (the third detection) within 30 minutes after the stop of the
outdoor unit described above (regardless of the first or the second stop), the outdoor unit will make an error stop, and the error
code "1102" will be displayed.
4) If the discharge temperature of 120°C [248°F] or more is detected more than 30 minutes after the previous stop of the outdoor
unit, the detection is regarded as the first detection, and the operation described in step 1 above will start.
5) For 30 minutes after the stop (the first stop or the second stop) of the outdoor unit, preliminary errors will be displayed on the
LED display.
3. Cause, check method and remedy
(1)
Gas leak, gas shortage
(2)
Overload operation
(3)
LEV failure on the indoor unit
(4)
BC controller LEV malfunction
Cooling only : LEV3
Cooling main : LEV1,3
Heating only or heating main : LEV3
Defrost : LEV3
(5)
BC controller SVM1 and 2 malfunction
→ Cooling only or defrost
(6)
BC controller SVA malfunction
→ Cooling only or cooling main
(7)
BC controller SVB malfunction
→ Heating only or heating main
(8)
Solenoid valve actuation failure (SV4a,
SV4b, SV4c, or SV4d)
→heating only, heating main
(9)
Port address setting error.
(10)
Closed ball valve
(11)
Outdoor fan (including fan parts) failure, mo-
tor failure, or fan controller malfunction
Rise in discharge temp. by low pressure
drawing for (3) - (11).
(12)
Gas leak between low and high pressures
(4-way valve failure, Compressor failure, So-
lenoid valve (SV1a) failure)
(13)
Thermistor failure
(TH4)
(14)
Input circuit failure on the controller board
thermistor
HWE1314A
Cause
Check method and remedy
Refer to the following page(s).[6-9 Evaluating and Adjusting
Refrigerant Charge](page 179)
Check operating conditions and operation status of indoor/
outdoor units.
Perform a heating operation and check the operation.
Cooling: LEV on the indoor unit
BC controller LEV1,3
SVM1,2
SVA,C
Heating: LEV on the indoor unit
BC controller LEV3
SVB
SV4a, SV4b, SV4c, SV4d
Refer to the following page(s). [8-8 Troubleshooting LEV
Problems](page 322)
Confirm the port address of the indoor unit.
Confirm that the ball valve is fully open.
Check the fan on the outdoor unit.
Refer to the following page(s). [8-7 Troubleshooting Outdoor
Unit Fan Problems](page 321)
Perform a cooling or heating operation and check the opera-
tion.
Refer to the following page(s). 3 [3-3 Functions of the Major
Components of Outdoor Unit(page 78)
Check the inlet air temperature on the LED monitor.
- 228 -
GB