[4-2 Outdoor Unit Circuit Board Components ]
4-2-6

Capacitor Board

(1) PURY-EP500YLM-A
CN102
Power supply detection
signal output
GND
SC-P
Bus voltage input(P)
note.1
CN106
Bus voltage input
N
P
R301∼R304
Rush current
protection resistor
1) When opening or closing the front panel of the control box, do not let it come into contact with any of the internal components.
Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that
the capacitor voltage (inverter main circuit) has dropped to 20 VDC or less. It takes about 10 minutes to discharge electricity
after the power supply is turned off.
2) Control box houses high temperature parts. Be well careful even after turning off the power source.
3) Perform the service after disconnecting the fan board connector (CNINV) and the connector board connector
(CN103). Before plugging in or unplugging connectors, check that the outdoor unit fan is not rotating and that the
voltage between SC-P and SC-N on the capacitor board is 20 VDC or less. The capacitor may collect a charge and
cause an electric shock when the outdoor unit fan rotates in windy conditions. Refer to the wiring nameplate for details.
4) To connect wiring to TB7, check that the voltage is 20 VDC or below.
5) Reconnect the connector (CNINV) back to the fan board and reconnect the connector (CN103) back to the connector board
after servicing.
HWE1314A
CN101
Input(L2)
Input(N)
Input(L3)
C101∼C108
Smoothing capacitor
- 106 -
CN103
Output
(Rectified L3-N current)
P
N
CN107
Output
(L3-N rectifier)
P
N
CN104
Output
(L3-N rectifier)
P
N
SC-N
Bus voltage input(N)
note.1
GB