Mitsubishi Electric PURY-P-YHM-A Installation Manual

Air-conditioners for building application outdoor unit, city multi, for use with r410a

Advertisement

Air-Conditioners For Building Application

OUTDOOR UNIT

PURY-P-YHM-A (-BS)
PURY-EP-YHM-A (-BS)

INSTALLATION MANUAL

For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit.
INSTALLATIONSHANDBUCH
Zum sicheren und ordnungsgemäßen Gebrauch der Klimageräte das Installationshandbuch gründlich durchlesen.
MANUEL D'INSTALLATION
Veuillez lire le manuel d'installation en entier avant d'installer ce climatiseur pour éviter tout accident et vous assurer d'une utilisation correcte.
MANUAL DE INSTALACIÓN
Para un uso seguro y correcto, lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado.
MANUALE DI INSTALLAZIONE
Per un uso sicuro e corretto, leggere attentamente questo manuale di installazione prima di installare il condizionatore d'aria.
INSTALLATIEHANDLEIDING
Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner installeert.
MANUAL DE INSTALAÇÃO
Para segurança e utilização correctas, leia atentamente este manual de instalação antes de instalar a unidade de ar condicionado.
E°XEIPI¢IO O¢H°IøN E°KATA™TA™H™
°È· ·ÛÊ¿ÏÂÈ· Î·È ÛˆÛÙ‹ ¯Ú‹ÛË,
ÂÁηٿÛÙ·ÛË Ù˘ ÌÔÓ¿‰·˜ ÎÏÈÌ·ÙÈÛÌÔ‡.
РУКОВОДСТВО ПО УСТАНОВКЕ
Для осторожного и правильного использования прибора необходимо тщательно ознакомиться с данным руководством по
установке до выполнения установки кондиционера.
MONTAJ ELKWTABI
Emniyetli ve doqru biçimde naswl kullanwlacaqwnw öqrenmek için lütfen klima cihazwnw monte etmeden önce bu elkitabwnw dikkatle okuyunuz.
·Ú·Î·Ï›ÛÙ ‰È·‚¿ÛÂÙÂ
ÚÔÛ¯ÙÈο ·˘Ùfi ÙÔ ÂÁ¯ÂÈÚ›‰ÈÔ ÂÁηٿÛÙ·Û˘
For use with R410A
ÚÈÓ ·Ú¯›ÛÂÙ ÙËÓ

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric PURY-P-YHM-A

  • Page 1: Outdoor Unit

    Air-Conditioners For Building Application OUTDOOR UNIT PURY-P-YHM-A (-BS) For use with R410A PURY-EP-YHM-A (-BS) INSTALLATION MANUAL For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit. INSTALLATIONSHANDBUCH Zum sicheren und ordnungsgemäßen Gebrauch der Klimageräte das Installationshandbuch gründlich durchlesen.
  • Page 2 [Fig. 6.0.1] [Fig. 6.0.2] <A> : Top view <B> : Side view <C> : When there is little space up to an obstruction A : Front B : Unit height C : Back <A> D : Air outlet guide (Procured at the site) <A>...
  • Page 3 [Fig. 8.1.1] <A> Without detachable leg A : M10 anchor bolt procured at the site. B : Corner is not seated. C : Fixing bracket for hole-in anchor bolt (3 locations to fix with screws). D : Detachable leg <B> With detachable leg [Fig.
  • Page 4 A [Standard] (mm) Unit combination A1 *1 A2 *1 Å Outdoor model ı High-pressure side Ç Low- pressure side ı High-pressure side Ç Low- pressure side ı High-pressure side Ç Low- pressure side Unit 1 Unit 2 ø15.88 ø19.05 P200 ø19.05 ø22.2 P250...
  • Page 5 [Fig. 9.2.2] <A> The piping from the outdoor units to twinning pipe must be made to slope downwards the twinning pipe. (high-pressure side only) <B> Slope of twinning pipe (high pressure side only) <C> Pipe connection example A : Downward slope B : Upward slope C : BC controller (standard or main) D : Twinning pipe...
  • Page 6 10.2 [Fig. 10.2.1] [Fig. 10.2.3] <A> Refrigerant service valve <B> Refrigerant service valve (High-pressure side/brazed type) (Low-pressure side/brazed type) A : Shaft B : Service port C : Cap D : Pinched connecting pipe severing portion * When not attaching a low-pressure twinning pipe. E : Pinched connecting pipe brazing portion A : Example of closure materials (field supply) B : Fill the gap at the site...
  • Page 7 10.3 [Fig. 10.3.1] [Fig. 10.3.2] A : Nitrogen gas A : System analyzer B : To indoor unit B : Low knob C : System analyzer C : Hi knob D : Low knob D : Valve E : Hi knob E : Low-pressure pipe F : Valve F : High-pressure pipe...
  • Page 8 11.2 [Fig. 11.2.1] A : Power source Power supply terminal block Terminal block for indoor – Terminal block for B : Transmission line (TB1) outdoor transmission line centralized control C : Earth screw Control box (TB3) (TB7) L1 L2 L3 N [Fig.
  • Page 9 [Fig. 11.3.2] <A> Change the jumper connec- CN41 CN40 tor from CN41 to CN40 *1 (51) (52) (01) (04) (55) (05) (06) <B> SW2-1:ON *2 TB02 TB02 TB15 TB15 TB15 M1 M2 S M1 M2 S M1 M2 M1 M2 M1 M2 S M1 M2 S M1 M2 S...
  • Page 10: Table Of Contents

    - Improper installation may cause the unit to topple and result in injury and damage to the unit. R410A refrigerant Always use ¿ lters and other accessories speci¿ ed by Mitsubishi Electric. • - Ask an authorized technician to install the accessories. Improper Caution: installation by the user may result in water leakage, electric shock, or ¿...
  • Page 11: Before Installation

    • Use refrigerant piping made of phosphorus deoxidized copper and • Never connect in reverse phases. copper alloy seamless pipes and tubes. In addition, be sure that the Never connect the Power Line L1, L2, and L3 to Terminal N. inner and outer surfaces of the pipes are clean and free of hazardous - If the unit is miss wired, when power is supplied, some electrical parts will sulphur, oxides, dust/dirt, shaving particles, oils, moisture, or any other...
  • Page 12: Combination Of Outdoor Units

    3. Combination of outdoor units Component units of PURY-P450 to P800 are listed below. Outdoor unit model Component unit model PURY-P200YHM-A(-BS) PURY-P250YHM-A(-BS) PURY-P300YHM-A(-BS) PURY-P350YHM-A(-BS) PURY-P400YHM-A(-BS) PURY-P450YSHM-A(-BS) PURY-P250YHM-A(-BS) PURY-P200YHM-A(-BS) PURY-P500YSHM-A(-BS) PURY-P250YHM-A(-BS) PURY-P250YHM-A(-BS) PURY-P550YSHM-A(-BS) PURY-P300YHM-A(-BS) PURY-P250YHM-A(-BS) PURY-P600YSHM-A(-BS) PURY-P300YHM-A(-BS) PURY-P300YHM-A(-BS) PURY-P650YSHM-A(-BS) PURY-P350YHM-A(-BS) PURY-P300YHM-A(-BS) PURY-P700YSHM-A(-BS) PURY-P400YHM-A(-BS) PURY-P300YHM-A(-BS)
  • Page 13: Con¿ Rmation Of Parts Attached

    5. Con¿ rmation of parts attached • This unit includes the following parts. Please check. • For usage methods, refer to item 10.2. 1 Connecting pipe 2 Connecting pipe 3 Connecting pipe 4 Connecting elbow ID ø25.4, ID ø22.2 ID ø25.4, OD ø19.05 ID ø25.4, ID ø28.58 ID ø19.05, OD ø19.05 <Low-pressure side>...
  • Page 14: Refrigerant Piping Installation

    Do not use any commercially available anti-oxidizing agent since it may cause pipe corrosion and degrading of the refrigerant oil. 1 Use the following materials for refrigeration piping. Please contact Mitsubishi Electric for more details. • Material: Use copper alloy seamless pipes made of phosphorus (Refer to item 10.2.
  • Page 15: Refrigerant Piping System

    Precautions for outdoor unit combinations 9.2. Refrigerant piping system Refer to [Fig. 9.2.2] for the positioning of twinning pipes. Connection example [Fig. 9.2.2] (P.5) [Fig. 9.2.1] (P.3, 4) <A> The piping from the outdoor units to twinning pipe must be made to slope Outdoor model High-pressure side downwards the twinning pipe.
  • Page 16: Precautions Concerning Piping Connection And Valve Operation

    10.2. Precautions concerning piping Refrigerant service valve piping On-site piping (low-pressure connecting pipe) connection and valve operation On-site piping (high-pressure connecting pipe) Twinning kit (sold separately) • Conduct piping connection and valve operation accurately and carefully. On-site piping (low-pressure connecting pipe: to BC controller) •...
  • Page 17: Airtight Test, Evacuation, And Refrigerant Charging

    Appropriate tightening torque: Caution: Outer Size of Make sure to seal-off the openings for the pipe and wire retrieval. diameter of hexagonal Service port • Small animals, rainwater, or snow entering through the openings may Cap (N·m) Shaft (N·m) copper pipe wrench (N·m) cause damage to the device.
  • Page 18: Thermal Insulation Of Refrigerant Piping

    Penetrations 10.4. Thermal insulation of refrigerant piping [Fig. 10.4.4] (P.7) <A> Inner wall (concealed) <B> Outer wall Be sure to add insulation work to refrigerant piping by covering high-pressure <C> Outer wall (exposed) <D> Floor (waterproo¿ ng) pipe and low-pressure pipe separately with enough thickness heat-resistant <E>...
  • Page 19: Wiring Transmission Cables

    11.3. Wiring transmission cables 1 Types of control cables 1. Wiring transmission cables • Types of transmission cables: Shielding wire CVVS, CPEVS or MVVS • Cable diameter: More than 1.25 mm • Maximum wiring length: Within 200 m • Maximum length of transmission lines for centralized control and indoor/outdoor transmission lines (Maximum length via outdoor units): 500 m MAX The maximum length of the wiring between power supply unit for transmission lines (on the transmission lines for centralized control) and each outdoor unit and system controller is 200 m.
  • Page 20: Wiring Of Main Power Supply And Equipment Capacity

    Unit Range Setting Method Indoor unit (Main) 01 to 50 Use the most recent address within the same group of indoor units. With an R2 system with sub BC controllers, set the indoor unit address in the following order: 1 Indoor units connected to the main BC controller 2 Indoor units connected to BC sub controller 1 3 Indoor units connected to BC sub controller 2 Set the indoor unit addresses so that all the addresses of 1 are smaller than those of 2, and that all...
  • Page 21: Test Run

    Caution: • Some installation sites may require attachment of an earth leakage breaker for the inverter. If no earth leakage breaker is installed, there is a danger of electric shock. • Do not use anything other than a breaker and fuse with the correct capacity. Using a fuse or wire of too large capacity may cause malfunction or ¿ re. Note: •...
  • Page 22 EP300 EP250 EP300 EP300 Refrigerant (R410A) 11.8kg 11.8kg 11.8kg 11.8kg Allowable pressure (Ps) HP: 4.15 MPa, LP: 2.21 MPa Net weight 265kg 265kg 265kg 265kg MANUFACTURER: MITSUBISHI ELECTRIC CORPORATION AIR-CONDITIONING & REFRIGERATION SYSTEMS WORKS 5-66, TEBIRA, 6-CHOME, WAKAYAMA CITY, JAPAN...
  • Page 23 This product is designed and intended for use in the residential, commer- cial and light-industrial environment. The product at hand is • Low Voltage Directive 2006/95/EC based on the following • Electromagnetic Compatibility Directive EU regulations: 2004/108/EC • Pressure Equipment Directive 97/23/EC Please be sure to put the contact address/telephone number on this manual before handing it to the customer.