Mitsubishi Electric PURY-P200YLM-A(1) Service Handbook page 391

Table of Contents

Advertisement

[8-15 BC Controller Maintenance Instructions ]
5. LEV
(1) Remove the service panel. (See figure at right.)
(2) Replace the LEV in trouble.
Secure enough service space in the ceiling for welding
operation, and conduct the work carefully.If required,
dismount the unit from the ceiling, and conduct the work.
6. Solenoid valve
(1) Remove the service panel. (See figure at right.)
(2) Remove the connector of the solenoid valve in trou-
ble.
(3) Remove the solenoid valve coil.
1) The coils on the solenoid valves SVA, SVB, SVM1,
SVM1b, SVM2, and SVM2b can be serviced through the
inspection door. SVC is accessible for replacement by
removing the four mounting screws on the rear panel
and removing the panel (if enough space is available on
the back). (SVM1 is present only on the G1, GA1, and
HA1 types, SVM2 on the GA1 and HA1 types, and
SVM1b and SVM2b on the HA1 type.)
HWE1314A
Work procedure
Work procedure
*Special care must be taken when replacing heavy parts.
Solenoid valve
- 380 -
Explanatory figure
LEV3
Explanatory figure
Double-pipe heat exchanger
CMB-1016V-G1
CMB-1016V-GA1
LEV1
SVM2
SVM2b
GB