Checking The Fan Inverter For Damage At No Load - Mitsubishi Electric PURY-P200YLM-A(1) Service Handbook

Table of Contents

Advertisement

[8-10 Troubleshooting Inverter Problems ]
8-10-9

Checking the Fan Inverter for Damage at No Load

Items to be checked
(1)
Turn off breaker.
*Turn power off without fail.
(2)
Disconnect the connector
CNINV from the fan board.
(3)
Set fan board switch SW1-1 to
ON.
(4)
Turn on breaker.
(5)
Operate unit.
After about 30 seconds under
no load with constant voltage
output, the code below will be
displayed indicating a position
error (5305, 5306).
Detail code: 132
Also, running with no load pro-
duces constant voltage of
about 160V.
HWE1314A
Phenomena
1)
Within 30 seconds from the start of
operation, an error other than a posi-
tion error (5305, 5306) (detail code
132) is detected.
2)
Less than 5V unbalance in the wir-
ing.
3)
No unbalanced voltage in the wiring.
After 30 second, detail code 132 is
produced and the system stops.
- 342 -
Remedy
Change fan board.
Change fan board.
Normal
*After checking, return
SW1&CNINV.