Wiring Diagram - Viessmann VITOFLAME 200 Service Instructions Manual

Oil burner
Hide thumbs Also See for VITOFLAME 200:
Table of Contents

Advertisement

Additional information

Wiring diagram

Control unit
components
Oil burner control unit
On−site
supply
Ext. fault
Op. lamp
Oil pre−heater
lamp
plug−in panel
15 to 40 kW
25/26
Flame monitor
Solenoid valve
Ignition
transformer
Burner motor
Oil pre−heater
Function sequence on start−up
Solenoid valve for
Burner
Flame
Ignition
ext. connection via
motor
monitor
transformer
separate adaptor
Control program LOA X4 . . . .
Control program LMO 14 .113
t0
Oil pre−heat time 2)
up to 2min
t0
Oil pre−heat time 2)
t1
Pre−flush time
approx.
13s
t1
Pre−flush time
t2
Safety time
max.
10s
t2
Safety time
t3
Pre−ignition time
approx.
13s
t3
Pre−ignition time
t3n Post−ignition time
approx.
15s
t3n Post−ignition time
if the flame is established
if the flame is established
2) Depending on the temperature of the
fuel oil supplied
Operating lamp
Solenoid valve
or hours run counter
on the oil pump
ext. (control unit)
Legend
A'
Start of oil pre−heat time
A'
Start−up
B
Timing of flame
being established
C
Operating position
D
Controlled switch−off
fA
Burner plug on the
control unit
F 1.1
Fuse in the control unit
F 6
High limit safety cut−out
F 7
Thermostat
S 1
Mains electrical switch
S 2
Test button
K 1
Burner relay
1 qW Plug−in terminals on the
oil burner control unit
up to 2min
Colour coding conforming to
approx.
16s
DIN/IEC 757
max.
10s
BK
black
approx.
15s
BN
brown
approx.
3s
BU
blue
1)
Connection of assembly modules and
accessories via system plug−in
connector fA (e.g. KNL, extension lead,
etc.)
2)
Connection of external safety
equipment via system plug−in
connector aBÖ
3)
Connection of external control
off−switch via system plug−in
connector aBÖ
4)
Connection for external burner ON
Please note:
This wiring diagram only applies in
conjunction with Viessmann
products.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents