Diagnosis; Troubleshooting - Viessmann VITOFLAME 200 Service Instructions Manual

Oil burner
Hide thumbs Also See for VITOFLAME 200:
Table of Contents

Advertisement

Diagnosis

Fault/system characteristics
Burner does not start (no fault
display), signal lamp does not
illuminate
Burner does not start (no fault
display), signal lamp
illuminates
Burner does not start up (with
fault)
Burner starts up, but no flame
is formed
Pump does not feed oil
Flashing code
Cause of fault
red
at LMO 14
No voltage
High limit safety cut−out
activated
10 × flashes
Faulty electrical
DDDDDDDDDD
connection, wires "L1"
and "N" interchanged or
faulty burner control unit
2 × flashes
Motor faulty
DD
2 × flashes
Coupler between motor
DD
and oil pump faulty
2 × flashes
Oil pump seized or stiff
DD
8 × flashes
Oil pre−heater faulty
DDDDDDDD
2 × flashes
Ignition electrodes
DD
incorrectly adjusted
2 × flashes
Ignition electrodes damp
DD
and contaminated
2 × flashes
Insulation of ignition
DD
electrode cracked
2 × flashes
Ignition transformer faulty Replace ignition transformer
DD
2 × flashes
Ignition cable faulty
DD
2 × flashes
Pump does not feed oil
DD
2 × flashes
Shut−off valves closed at
DD
filter or in oil pipe
2 × flashes
Filter blocked
DD
2 × flashes
Coupler between motor
DD
and pump faulty
2 × flashes
Leak in suction line or
DD
filter cup
2 × flashes
Oil flow and return hoses
DD
interchanged
2 × flashes
Vacuum in suction line too
DD
high (higher than 0.35 bar)
2 × flashes
External fuel oil valve
DD
faulty

Troubleshooting

Check
Check fuse or connector aBÖ in control
unit, or check electrical connections,
setting of heating system on/off switch
on control unit and mains electrical
isolator
Press reset button on boiler control unit
Check electrical connection
If phases are correctly connected,
replace burner control unit
Replace motor
Replace coupler
Clean or, if necessary, replace oil pump
Replace oil pre−heater
Adjust correctly (see page 12)
Clean ignition electrode block
Replace ignition electrode block
Replace ignition cable
Install pressure and vacuum gauges on
pump and check build−up of pressure
(see following paragraph)
Open valves
Clean filter (pre−filter and pump filter)
Replace coupler
Tighten connections
Check oil pipes and connections for leaks
and tighten if necessary
Connect correctly acc. to instructions on
pump
Check cross−section of oil pipes. Replace
filter
Check external fuel oil valve
Check and, if necessary, replace external
oil valve
19