The following will be displayed when the START/STOP key on the MAIN MENU is pressed (Jump into OPERATION
MENU):
1) Startup/Shutdown Guidance (Figure 4-3 to Figure 4-5)
The display indicates the Startup and Shutdown guidance for the UPS system. If this operation is PIN protected, the
user is required to enter the security PIN before the screen can be accessed.
When in remote mode, the message "REMOTE operating model" will appear on this Screen. The user cannot operate
the start and stop functions without changing the setup from remote mode to local mode.
When bypass voltage is abnormal, the message "Bypass voltage abnormal" will appear.
-Start: When the bypass voltage is abnormal, the LCD asks the operator if an interrupted transfer is acceptable
(Load may be lost).
-Stop: When the bypass voltage is abnormal, the user cannot transfer from inverter to bypass line.
G9000 Series UPS 300-750kVA Installation and Operation Manual – 61480-017
LED: LOAD ON INV

Figure 4-2 Main Screen

Figure 4-3 Startup/Shutdown Guidance

27