7.3

EPO and Remote Shutdown

EPO (Emergency Power Off): TB1-14, -15
The EPO is a NO (Normally Open) dry contact switch. When the EPO is closed, the Input circuit breaker to the UPS
opens and all power to the unit is removed, including backup power from the batteries.
Remote Shutdown: TB1-16, -17
The Remote Shutdown is a NO (Normally Open) dry contact switch. When the Remote Shutdown switch is closed, the
UPS transfers from Normal/Backup to Bypass after a 1 – 2 sec. detection delay. (See the diagram below)
When the closed Remote Shutdown switch is opened, the UPS transfers from Bypass back to it's initial state (Normal/
Backup) after a 1 – 2 sec. detection delay.
If the UPS is in bypass when the Remote Shutdown is closed, no action is taken.
7.4

Cable Size and Tightening Torque

Use the following table to select the recommended wire size and terminal lug tightening torque for I/O wire connections. Use
90 °C copper conductors for all Input, Output, and Ground wiring.
Item
AC Input Lines
AC Output Lines
AC Output Neutral
Ground
EPO Switch
Remote Switch
Note: Wire size is presented as the recommended size followed by a bold number in () indicating the maximum wire size the terminal
block can accommodate. See Appendix C for knock-out hole sizes on the back of each model.
7.5

Battery Cabinet Connections

Optional external battery cabinets can be used to extend the backup time of the UPS beyond that available with the internal
batteries. The external battery cabinets connect to the UPS via Anderson-style connectors. See Section 20.
1600XPi Series UPS Installation and Operation Manual – 60616-014
Detection Delay
1-2 Sec.
Remote Status
Open
Switch
UPS Mode
Normal / Backup Mode
FIGURE 7.1:
Terminal
Number
3.6 kVA
1 and 2
10 (8)
4, 5, and 7
12 (8)
6
12 (8)
3 and 8
12 (8)
14 and 15
16
16 and 17
16
Closed
Bypass Mode
REMOTE STATUS SHUTDOWN TIMING
Cable Size
5.2 –6 kVA
8 kVA
(1/0)
8 (8)
8
(1/0)
10 (8)
8
(1/0)
10 (8)
8
10 (8)
(1/0)
8
16
16
16
16
Detection Delay
1-2 Sec.
AWG
10 kVA
14 – 18 kVA
(1/0)
4 (1/0)
6
(1/0)
4 (1/0)
6
(1/0)
)
6
4 (1/0)
(1/0)
)
4 (1/0)
6
16
16
16
16
Tightening
Torque
lb.-in. (N•m)
22 kVA
1 (1/0)
14.2 (1.56)
1 (1/0)
14.2 (1.56)
1 (1/0)
14.2 (1.56)
1 (1/0)
14.2 (1.56)
16
9.0 (0.99)
16
9.0 (0.99)
15