Operation & Service Manual
Installation Commissioning
Carrier Transicold Europe
Settings
TXV setting
31/03/07
1. Connect manifold to evaporator outlet fitting.
2. Install a sensor on the expansion valve bulb location.
3. Run the unit on COOLING mode.
4. Correct superheat:
Turn anti-clockwise to increase flow & decrease
superheat
Turn clockwise to decrease flow and increase
superheat.
TXV adjustment
8°C at box temperature 0°C
Viento 200
(14.4°F at box T° : 32°F)
Viento 300
4°C at box temperature -20°C
Viento 350
(7.2°F at box T° : -4°F)
Viento - Installation/Rev- #54/54