Carrier INFINITY 24ANA Installation Instructions Manual
Carrier INFINITY 24ANA Installation Instructions Manual

Carrier INFINITY 24ANA Installation Instructions Manual

Infinity series air conditioners with puronr refrigerant 2 to 5 nominal tons (sizes 24 to 60)
Hide thumbs Also See for INFINITY 24ANA:

Advertisement

24ANA
Infinityt Series Air Conditioners
with Puronr Refrigerant
2 to 5 Nominal Tons (Sizes 24 to 60)
NOTE: Read the entire instruction manual before starting the
installation.
Unless otherwise noted, information in these installation
instructions pertain to both 2
Information that is unique to the 24ANA1 series will be identified
as such; likewise information that is unique to the 24ANA7 series
will also be identified.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory- -authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Use quenching cloth for brazing operations.
Have fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions included in
literature and attached to the unit. Consult local building codes and
current editions of the National Electrical Code (NEC) NFPA 70.
In Canada, refer to current editions of the Canadian electrical code
CSA 22.1.
Recognize safety information. This is the safety- -alert symbol
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.
Understand these signal words; DANGER, WARNING, and
CAUTION. These words are used with the safety- -alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death.
which could result in personal injury or death. CAUTION is used
to identify unsafe practices which may result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability, or
operation.
CAUTION
!
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and
wear appropriate protective clothing and gloves when handling
parts.

Installation Instructions

4ANA1
and 24ANA7 series units.
WARNING signifies hazards
Indoor Thermostat Control Options
Model
24ANA7
24ANA1
* Units containing circuit board HK38EA015 or newer.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF position.
There may be more than 1 disconnect switch. Lock out and
tag switch with a suitable warning label.
!
! !
.
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could result in personal injury,
death and/or equipment damage.
Puron refrigerant systems operate at higher pressures than
standard R- -22 systems. Do not use R- -22 service equipment
or components on Puron equipment.
Infinity
Standard 2--- stage
Control
Thermostat
Yes
Yes
WARNING
WARNING
Yes
Yes*

Advertisement

Table of Contents
loading

Summary of Contents for Carrier INFINITY 24ANA

  • Page 1: Installation Instructions

    24ANA Infinityt Series Air Conditioners with Puronr Refrigerant 2 to 5 Nominal Tons (Sizes 24 to 60) Installation Instructions NOTE: Read the entire instruction manual before starting the installation. Unless otherwise noted, information in these installation 4ANA1 instructions pertain to both 2 and 24ANA7 series units.
  • Page 2: Installation Recommendations

    INSTALLATION RECOMMENDATIONS NOTE: In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment. 1. Locate unit away from windows, patios, decks, etc. where unit operation sound may disturb customer. 2. Ensure that vapor and liquid tube diameters are appropriate for unit capacity.
  • Page 3: Operating Ambient

    On rooftop applications, locate unit at least 6 in. (152.4 mm) above roof surface. Operating Ambient The minimum outdoor operating ambient in cooling mode is 55_F/12.78_C without low ambient cooling enabled, and the maximum outdoor operating ambient in cooling mode is 125_F/51.67_C.
  • Page 4 Accessory Accumulator Compressor Start Assist Capacitor and Relay} Not required for 24ANA1 models. Crankcase Heater Evaporator Freeze Protection (Low Ambient not allowed with non --- Liquid Line Solenoid Valve Standard with Infinity Control (Low Am- Low--- ambient Control bient not allowed with non ---communi- Puron Balance Port Hard Shut--- off TXV Standard with Infinity Control (Low Am- Winter Start Control...
  • Page 5: Electrical Shock Hazard

    Refrigerant tubes and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns. The alternate triple evacuation method may be used. See Service Manual for triple evacuation method. Always break a vacuum with dry nitrogen._ Deep Vacuum Method The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth.
  • Page 6: Make Airflow Selections

    ON or AUTO mode, as desired. Operate unit for 15 minutes. Check system refrigerant charge. NOTE: Non- -communicating (non- -Infinity) Carrier electronic thermostats are equipped with a 15- -minute staging timer. This timer prevents the 2- -stage system from operating at high- -stage until unit has been operating in low- -stage for 15 minutes unless there is at least a ±5_F (±2.78_C) difference between room...
  • Page 7: System Functions And Sequence Of Operation

    System Functions And Sequence Of Operation The outdoor unit control system has special functions. The following is an overview of the 2- -stage control functions: Cooling Operation 24ANA7 and 24ANA1 (containing circuit board HK38EA015 or newer) models utilize either a 2- -stage cooling indoor thermostat or an Infinity communicating User Interface.
  • Page 8: Crankcase Heater Operation

    Compressor Operation on 24ANA1 Models The basic scroll design has been modified with the addition of an internal unloading mechanism that opens a by- -pass port in the first compression pocket, effectively reducing the displacement of the scroll. The opening and closing of the by- -pass port is controlled by an internal electrically operated solenoid.
  • Page 9: Check Charge

    Check Charge All 24ANA units must be charged in high stage only. Factory charge amount and desired subcooling are shown on unit rating plate. Charging method is shown on information plate inside unit. To properly check or adjust charge, conditions must be favorable for subcooling charging.
  • Page 10 The control is shipped with the brownout active. The change in status is remembered until toggled to a new status. A power down/power up sequence will not reset the status. It may be necessary to do the toggle twice to cycle to the desired state of the defeat.
  • Page 11: Major Components

    (Winding Resistance at 70_F ± 20_ / 21.11_C ± 11.11_C) Winding 24ANA724 Start (S---C) 2.74 Run (R ---C) 0.80 Winding 24ANA124 Start (S--- C) 1.40 Run (R --- C) 1.32 MAJOR COMPONENTS 2- - Stage Control The 2- -stage control board controls the following functions: - - Low- - and high- -stage compressor contactor operation - - Outdoor fan motor operation - - Low ambient cooling...
  • Page 12: Final Checks

    OAT Thermistor must be locked in place with spherical nib end facing to- wards the front of the control box Fig. 8 - - Outdoor Air Thermistor (OAT) Attachment FINAL CHECKS IMPORTANT: Before leaving job, be sure to do the following: 1.
  • Page 13: Status Codes

    Status Codes Table 6 shows the status codes flashed by the amber status light. Most system problems can be diagnosed by reading the status code as flashed by the amber status light on the control board. The codes are flashed by a series of short and long flashes of the status light.
  • Page 14: Wiring Diagram

    Humidify Outdoor Air Temp Remote Room Sensor OAT/RRS Return SRTN Edge Thermidistat Models TP---PRH ---01 & TP---NRH ---01 Fig. 10 - - Thermidistat Wiring with 2- -Stage Puron refrigerant Air Conditioner Two-Stage Thermidistat Air Conditioner Heat Stage 2 O/B W2...
  • Page 15: Puronr Refrigerant Quick Reference

    User Interface Fig. 11 - - Infinity Furnace or Fan Coil Wiring with Communicating 2- -stage AC PURONR (R- -410A) REFRIGERANT QUICK REFERENCE GUIDE S Puron refrigerant operates at 50- -70 percent higher pressures than R- -22. Be sure that servicing equipment and replacement components are designed to operate with Puron refrigerant S Puron refrigerant cylinders are rose colored.
  • Page 16 Catalog No: 24ANA ---6SI Copyright 2009 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 07/09 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.