CHAPTER 4 APPLIED OPERATION
Output
JSetup
• Setting heating and cooling control
Operation Procedure
Initial setting level
Standard/heating
and cooling
• Setting dead band
Operation Procedure
Adjustment level
Dead band
• Setting cooling coefficient
Operation Procedure
Adjustment level
Cooling
coefficient
4–10
Control output
Control output 2 side P
1 side P
0
Set point
Control output 1 side P0.8
To set heating and cooling control, set the standard/heating and cooling",
dead band" and cooling coefficient" parameters.
standard/heating and cooling" = heating and cooling"
(1) Press the
tion level" to the initial setting level".
(2) Select standard heating and cooling control" in the initial setting
level".
: Standard control

: Heating and cooling control

Dead band" = 5"
(1) Select dead band" in the adjustment level".
(2) Use the
The setting range is 199.9 to 999.9.
Cooling coefficient = 10
(1) Select cooling coefficient" in the adjustment level".
In this example, set the parameter to 10".
(2) Use the
The setting range is 0.01 to 99.99.
Output
Control output 1 side
P1.0
Control output
1 side P
PV
0
key for at least three seconds to move from the opera
keys to set the parameter to 5.0".
keys to set the parameter to 10.00".
Control output 1 side
P1.0
Control output 2 side P
PV
Set point
Control output 1 side P1.5