E5GN
Temperature controller
EN
Instruction Manual
Thank you for purchasing the OMRON E5GN tempera-
ture controller. Read this manual carefully before using
the controller and always keep it close at hand while the
controller is in use.
OMRON CORPORATION
©All Rights Reserved
For detailed operating instructions, please refer to
the E5GN User's Manual.
Safety Precautions
●Key to Warning Symbols
Indicates a potentially hazardous situation which, if
not avoided, is likely to result in minor or moderate
injury or property damage. Read this manual
CAUTION
CAUTION
CAUTION
carefully before using the product.
0682727-0H
N6
■Wiring
●Dimensions
Dimensions (mm)
48
3
CMW
STOP
OUT
* Terminal part can be removed for maintenance without disconnecting the terminal wiring.
●Names of parts on front panel
• Level key
Use this key to change levels:
key and the M key together for
• Press the
at least 3 seconds to switch to protect level.
• Mode key
Press this key to change the contents of the
display

■Operation menu

●Input type
Setting range
Input type
Input
Setting
Platinum
0
–200 to 850(℃)
resistance
Pt100
1
–199.9 to 500.0(℃)
thermometer
2
0.0 to 100.0(℃)
3
–199.9 to 500.0(℃)
JPt100
4
0.0 to 100.0(℃)
Input type
Input
Setting
Setting range
Thermocouple
0
K
–200 to 1300(℃)
1
–20.0 to 500.0(℃)
2
–100 to 850(℃)
J
3
–20.0 to 400.0(℃)
T
4
–200 to 400(℃)
17
–199.9 to 400.0(℃)
E
5
0 to 600(℃)
L
6
–100 to 850(℃)
U
7
–200 to 400(℃)
18
–199.9 to 400.0(℃)
8
N
–200 to 1300(℃)
9
R
0 to 1700(℃)
10
0 to 1700(℃)
S
11
100 to 1800(℃)
B
Infrared
10 –70℃
12
0 to 90(℃)
Thermosensor
60 –120℃
13
0 to 120(℃)
ES1B
115 –165℃
14
0 to 165(℃)
140 –260℃
15
0 to 260(℃)
Analog input
0 to 50mV
Use the following ranges for scaling:
16
–1999 to 9999, –199.9 to 999.9
• Default = "0"
●Alarms
Alarm output function
Alarm type
Setting
Positive alarm value (X)
0
No alarm function
Output off
L H
*1
1
ON
Deviation upper/lower limit
OFF
SP
X
2
Deviation upper limit
ON
OFF
SP
X
3
ON
Deviation lower limit
OFF
SP
L H
*1
4
ON
Deviation upper/lower range
OFF
SP
L H
Deviation upper/lower limit
*1
5
ON
standby sequence ON
OFF
SP
X
Deviation upper limit
6
ON
standby sequence ON
OFF
SP
X
Deviation lower limit
7
ON
standby sequence ON
OFF
SP
X
8
ON
Absolute value upper limit
OFF
0
X
9
ON
Absolute value lower limit
OFF
0
X
Absolute value upper limit
10
ON
standby sequence ON
OFF
0
X
Absolute value lower limit
11
ON
standby sequence ON
OFF
0
*1: Upper and lower limits can be set for parameters 1, 4 and 5 to provide for
different types of alarm. These are indicated by the letter "L" and "H".
• Default = "2"
●Controller attribute read-out
Use this function to check the controller's format
and communication buffer size.
Command
Sub-ad-
SID
Node
MRC
SRC
ETX BCC
dress
No.
STX
0 0
0
0 5
0 3
Response
Sub-ad-
Termina-
MRC
SRC
Response
Node
No.
dress
tion code
code
STX
0 5
0 3
1
2
2
2
2
2
4
●Warning Symbols
CAUTION
Do not touch terminals when voltage is applied.
Electric shock hazard
Do not allow metal fragments or lead wire scraps to fall inside this product. This may cause electric shock, fire
or malfunction.
Do not use this product where subject to flammable or explosive gas.
Doing so may cause explosion.
Never disassemble, repair or modify the product. This may cause electric shock, fire or
malfunction.
CAUTION - Risk of Electrical Shock
a) Devices are Open Type, Listed Process Control Equipment and must be mounted in an enclosure.
b) More than one disconnect switch may be required to de-energize the equipment before servicing.
c) Signal inputs are SELV, limited energy.
d) Caution - To reduce risk of fire or Electrical shock, Do not interconnect the outputs of different Class 2
circuits.
The life expectancy of the output relay varies considerably according to its the output relay within its rated load
and electrical life expectancy, if the output relay is used beyond its life expectancy, its contacts may become
fused or burned.
Use copper stranded or solid wire only. For terminals 1-6 use 24-14 AWG. For terminals 7-9 use 28-22 AWG.
Tightening torque: Terminals 1-6: 0.24N•m, 2 inch lbs(max), Terminals 7-9: 0.13N•m, 1.2 inch lbs(max)
Loose screws may cause malfunction.
Correctly set the settings on the temperature controller matched to the control target.If the settings are not
compatible with the control target, the product may operate in an unexpected manner, resulting in damage to
the product or an accident.
To maintain safety in the event of malfunction of the temperature controller, we recommend taking safety
measures, for example, installing an excessive temperature rise prevention alarm on a separate line. If
malfunction prevents control, this may result in a major accident.
WARNING: To reduce the risk of electric shock or fire, install in a Pollution Degree 2 environment (a
controlled environment relatively free of contaminants).
Suitability for Use
OMRON shall not be responsible for conformity with any standards, codes, or regulations that
apply to the combination of the products in the customer's application or use of the product.
Take all necessary steps to determine the suitability of the product for the systems, machines,
and equipment with which it will be used.
Know and observe all prohibitions of use applicable to this product.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT
ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE
OMRON PRODUCT IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL
EQUIPMENT OR SYSTEM.
See also Product catalog for Warranty and Limitation of Liability.
In the pack:
• Main unit
• Watertight packing
• Adapter
• Instruction manual
100
• No.1 display
Process value or set data symbol
• No.2 display
CMW
STOP
OUT
Set point, set data read-out value or changed
input value
• Up and Down keys
Use the keys to change the values displayed on
the No.2 display.
Each press of U key increments or advances
the values displayed on the No.2 display.
Each press of D key decrements or returns the
values displayed on the No.2 display.
Operation stopped.(control/alarm are both stopped.)
●Initial setting level
/–300 to 1500(
F)
Input type *2
/–199.9 to 900.0(
F)
/0.0 to 210.0(
F)
Scaling upper limit
*7
/–199.9 to 900.0(
F)
(only when setting analog input)
/0.0 to 210.0(
F)
Scaling lower limit
*7
(only when setting analog input)
/–300 to 2300(
F)
Decimal point
/0.0 to 900.0(
F)
*7
(only when setting analog input)
/–100 to 1500(
F)
/0.0 to 750.0(
F)
°C/°F selection
*7
/–300 to 700(
F)
(C stands for Celsius, F for Fahrenheit)
/–199.9 to 700.0 (
F)
/0 to 1100(
F)
Set point upper limit
/–100 to 1500(
F)
/–300 to 700(
F)
/–199.9 to 700.0 (
F)
Set point lower limit
/–300 to 2300(
F)
/0 to 3000(
F)
In ON/OFF control =
/0 to 3000(
F)
In 2-PID control =
/300 to 3200(
F)
Standard control =
/0 to 190(
F)
s-hc
*7
Heating and cooling control =
stnd
/0 to 240(
F)
(Select standard control or healing
and cooling control as required)
/0 to 320(
F)
Self-tuning ON =
/0 to 500(
F)
*7
Self-tuning OFF =
Control period (control output 1)
*7
(Unit: Seconds)
Control period (control output 2)
c-cp
*7
20
(Unit: Seconds)
In Reverse operation(heat) =
Negative alarm value (X)
In Direct operation(cool) =
*7
Alarm 1 type: Specified models only
Vary with "L", "H" values
Initial setting level enables users to specify their preferred operating
X
conditions (input type, alarm type, control method, etc.)
ON
OFF
SP
*2: Refer to the adjoining tables for details of input types and alarm types.
X
ON
OFF
SP
Vary with "L", "H" values
●Communication setting level
Vary with "L", "H" values
X
Communication
ON
OFF
unit No.
SP
X
Communication
ON
OFF
rate
SP
X
ON
OFF
Data length
0
X
ON
OFF
0
Make sure the communication settings (Communication rate, etc.)
X
ON
match those of the Host Computer.
OFF
0
●Command format
X
ON
OFF
0
For CompoWay / F
Node
SID FINS-mini
Sub-
No.
address
Command text
STX
STX
Code (H'02) to indicate the head of the communication frame (text).
If STX is received a second time while receiving a communication, it
indicates that the communication is starting again from that point.
Node No.
Specifies the transmission destination unit No. Settings range from
00 to 99.
Sub-address
"00" (Fixed)
SID
Service ID, "0" (Fixed)
FINS-mini
Contains command contents such as read and write values, and sta-
command text
tus data
ETX
Code (H'03) indicating the end of the text.
BCC
Block check character
Error check method used by FINS-mini.
Each byte from node No. through ETX has an XOR (exclusive OR)
value
Format
Buffer size
ETX
BCC
10
4
1
1
(1) Do not use this product in the following places:
• Places directly subject to heat radiated from heating equipment.
• Places subject to splashing liquid or oil atmosphere.
• Places subject to direct sunlight.
• Places subject to dust or corrosive gas (in particular, sulfide gas and
ammonia gas).
• Places subject to intense temperature change.
• Places subject to icing and condensation.
• Places subject to vibration and large shocks.
(2) Use/store within the rated temperature and humidity ranges.
Provide forced-cooling if required.
(3) To allow heat to escape, do not block the area around the product.
Do not block the ventilation holes on the product.
(4) Be sure to wire properly with correct polarity of terminals.
(5) Use AWG24 to AWG14 leads for terminal Nos. 1 to 6 and AWG28 to AWG
22 for terminal Nos. 7 to 9 (with lead cover peel back allowance of 5 or 6
mm).
(6) Do not wire the terminals which are not used.
(7) Allow as much space as possible between the controller and devices that
generate a powerful high-frequency or surge.
Separate the high-voltage or large-current power lines from other lines, and
avoid parallel or common wiring with the power lines when you are wiring to
the terminals.
(8) Use this product within the rated load and power supply.
(9) Make sure that the rated voltage is attained within two seconds of turning the
power ON.
(10) Make sure the controller has 30 minutes or more for warm up.
(11) When executing self-tuning, turn the load and the unit ON simultaneously,
or turn the load ON before you turn the controller ON.
(12) A switch or circuit breaker should be provided close to this unit.
The switch or circuit breaker should be within easy reach of the operator,
and must be marked as a disconnecting means for this unit.
(13) When you have removed the terminal block, never touch nor apply shock to
the terminals and the electronic components inside.
(14) Cleaning: Do not use paint thinner or the equivalent. Use standard grade
alcohol to clean the product.
●Installation
Individual mounting (mm)
When waterproofing is
required, be sure to mount
the controller separately.
Attach the waterproof
44.8
packing from the terminal
side and then insert the
controller to the panel.
Recommended panel
thickness is 1 to 5 mm.
+0.6
45
 0
• Insert the controller through the hole in the panel. Push
the adapter on from the rear and fasten temporarily, re-
moving any gap between the controller, panel and adap-
ter. Finally, secure two fixing screws alternately keeping
the torque to between 0.29 to 0.39 N•m.
• Make sure that the surrounding temperature does not exceed the
allowable operating temperature given in the specifications espe-
cially when two or more controllers are mounted.
• °C / °F : temperature unit
The temperature unit is displayed when
the displayed value is a temperature.
When this parameter is
set to "°C", "°c" is displayed,
and when set to "°F", "°f" is displayed.
This flashes while ST(Self-Tuning) is
activated.
• AL : Alarm 1 output indicator
Lights when alarm 1 output is ON.
*5
●Operation level
°C=
*7
°F=
*7
*7
Operation level should normally be used
during operations.
stnd
h-c
Hold
and
M keys down for
at least 1 second
●Protect level
*2
*3
Restricts which settings can be
displayed or changed, and restricts
change by key operation.
Press  
●Operation / Adjustment protection
(less than 1 second)
The following table shows the relationship between settings and
*4
protect limits related to Operation level and Adjustment level.
Stop bit
Operation level
Parity
Adjustment level
Default setting : 0
◎:Can be displayed and changed
○:Can be displayed
×:Can not be displayed and change to other levels not possible
●Initial setting/Communications protection
This protect level restricts movement to the initial setting level,
communications setting level and advanced function setting level.
Initial setting
Set value
0
ETX
BCC
1
2
Default setting : 1
○:Change to other levels possible
×:Change to other levels not possible
●Setting change protection
Setting changes by key operation are restricted.
OFF "off": Setting can be changed by key operation
ON "on"
: Setting cannot be changed by key operation
(Protect level settings can all be changed.)
●Termination code (For CompoWay / F)
Termina-
tion code
00
Normal termination
0F
Command error
10
Parity error
11
Framing error
12
Overrun
13
BCC error
14
Format error
Sub-address error
16
Frame length error
18
Precautions for safety use
●Connections
Side-by-side mounting(waterproof not possible) (mm)
+1
(48 x number of units –2.5)
 0
• Since the voltage output (control output) is not electrically insulated from the internal
• Power supply, input, output, and communication terminals (for models with
CMW
STOP
●Adjustment level
POWER ON
*7
*7
PV/SP
*7
Run/Stop
When control start =
When control stop =
*7
Alarm value 1 *4
*7
Alarm value upper limit 1
*3
*7
Alarm value lower limit 1
*3
*7
Hold
and
M keys down for
at least 3 seconds
Adjustment level is for entering set
Operation / adjustment
values and shift values for control.
protect
*3: Applicable only to models with alarm functions
Initial /
Communication
*4: Applicable only to models with a communications function
protect
*5: Operation is stopped when moved to the initial setting level. (control/alarm are
both stopped.)
Setting change protect
*7: The grayed-out setting items may not be displayed according to the models and setting.
●AT (auto-tuning)
• AT in Adjustment level
Designate "on: AT execute" to execute
AT and "off: AT cancel" to cancel AT.
●Error display (trouble shooting)
Set value
When an error has occurred, the No.1 display alternately indicates error
Level
0
1
2
3
codes together with the current display item.
Process value
No.1 display
Set point
Others
×
×
×
×
×
(S. Err)
  
(E111)
Communications
Advanced function
If the input value exceeds the display limit (–1999(–199.9) to
9999(999.9)), though it is within the control range, [[[[ will be displayed
level
setting level
setting level
under –1999(–199.9) and ]]]] above 9999(999.9). Under these
conditions, control output and alarm output will operate normally.
×
Refer to "E5GN User's Manual" for details of control range.
×
×
×
*6: Error shown only for "Process value / Set point". Not shown for other
status.
Name
Description
Unexecutable command received
Parity mismatch
No stop bit detected
Receive buffer overflowed
BCC mismatch
Incorrect data length
Incorrect sub-address
When the receive frame exceeds the specified byte count
●Specifications
Power supply voltage
100-240V AC type
24V AC/DC type
Operating frequency
50-60Hz
Operating voltage range
85 to 110% of the rated voltage
Power consumption
Approx. 7VA (AC100-240V)
Approx. 4VA (AC24V)
Approx. 2.5W (DC24V)
Indication accuracy
Thermocouple, platinum resistance
thermometer:
(±0.5 % of indication value or ±1°C,
which is greater) ±1 digit max.
Analog input:
±0.5 % FS ±1 digit max.
Control output 1
Relay output: SPST-NO,
250VAC 2A (resistive load)
Voltage output 12VDC 21mA
Electrical life of relay:
100,000 operations
Control method
ON/OFF or 2-PID control
Alarm output
SPST-NO, 250 VAC, 1 A(resistive load),
(control output 2)
electrical life:100,000 operations
Ambient temperature
–10 to 55°C
(Avoid freezing or condensation)
Ambient humidity
RH 25 to 85%
Storage temperature
–25 to 65°C
(Avoid freezing or condensation)
Altitude
Max. 2,000m
Recommended fuse
T2A, 250V AC, time-lag,
low-breaking capacity
Weight
Approx. 90g (main unit only)
Installation environment
Setup category II, pollution
degree 2 (as per IEC61010-1)
(The applicability of the electric terminal varies with the type of machine.)
1
2
3
4
5
6
7
8
9
Control output 1
TC
(+)
(−)
B
A
Input power supply:
Relay output
RS-485
Communications
•100 to 240V AC Type
250V AC 2A
function
(resistive load)
•24V AC/DC Type
PT
A
B
B
Alarm
1/Control output
2
250V AC 1A
Voltage output
(resistive load)
12V DC 21mA
Analog input
(resistive load)
wiring, one or other of the control output terminals must be left unearthed when using
an earthed thermocouple thermometer. (Connection makes measurements unreliable
due to sneak currents.)
communications) have basic insulation between them.
When double insulation is required, apply supplemental insulation defined in
IEC 60664 that is suitable for the maximum operating voltage with clearances
or solid insulation.
Operation indicators
• CMW: communications writing enable/disable indicator
Lights when communications writing is "enabled"
and is out when it is "disabled".
OUT
• STOP: control stop indicator
Lights when "Run/Stop" is stopped during opera-
tion.
During control stop, functions other than control
output are valid.
• OUT: Control output 1/Control output 2 indicator
Lights when control outputs 1 and 2 are ON or
either of them is ON.
AT execute =
*7
Derivative time
(Unit: secs)
AT cancel =
c-sc
Communication write
*7
Cooling coethcient
1.00
*4
Temperature input shift
c-db
*7
Dead band
0.0
(Unit:°C or °F)
Input shift upper limit
Manual reset value
(When Infrared Thermo-
*7
(Unit: %)
sensor ES1A selected)
Input shift lower limit
Hysteresis
(When Infrared Thermo-
*7
(Control output 1)
sensor ES1A selected)
Hysteresis
chys
Proportional band
*7
1.0
(Control output 2)
Integral time
Only the value set to the "ins: temperature input shift"
(Unit: secs)
parameter is applied to the entire temperature input
range. When the process value is 200 °C, the process
value is treated as 201.2 °C after input shift if the input
shift value is set to 1.2 °C.
The process value is treated as 198.8 °C after input shift
if the input shift value is set to –1.2 °C.
After shift
Temperature
Input shift value: (1.2°C)
501.2℃
500.0℃
201.2℃
Before shift
200.0℃
-18.8℃
-20.0℃
Sensor input
-20.0℃
200.0℃
500.0℃
(Ex.) Thermocouple input type, Input type:1,
Temperature unit:°C, temperature input shift:1.2 °C
"AT execute" "at" flashes
U
D
"AT cancel"
Also when AT execution ends, the display
automatically returns to "off".
Status at error
Meaning
Action
Control
Alarm
output
Operates
Check the wiring of inputs, disconnections,
as above
Input error
OFF
shorts and input type.
the upper
*6
limit.
After the correction of input error, turn the power
OFF then back ON again. If the display remains
the same, the controller must be repaired. If the
A/D converter error
OFF
OFF
display is restored to normal, then a probable
*6
cause can be external noise affecting the control
system. Check for external noise.
Turn the power OFF then back ON again. If the dis-
play remains the same, the controller must be re-
paired. If the display is restored to normal, then a
OFF
OFF
Memory error
probable cause can be external noise affecting the
control system. Check for external noise.

■Other functions

In addition to the aforementioned, there are alarm hysteresis,
automatic return of display mode and others in the advanced
setting level.
Refer to "E5GN User's Manual" for details.
For communications details, please refer to "E5AN/EN/CN/GN
communications User's Manual".
OMRON ELECTRONICS. LLC
ONE COMMERCE DRIVE SCHAUMBURG, IL 60173-5302 U.S.A
Phone 1-847-843-7900
FAX:1-847-843-7787
EUROPEAN H.Q : OMRON EUROPE B.V
Wegalaan 67-69 P.O.BOX.13 2130 AA HOOFDDORP THE
NETHERLANDS
Phone 31-23-5681300
FAX 31-23-5681388
OMRON ASIA-PACIFIC PTE.LTD.
83, Clemenceau Avenue, #11-01, UE Square, Singapore
239920 SINGAPORE
Phone 65-6-835-3011
FAX 65-6-835-2711

Advertisement

loading

Summary of Contents for Omron E5GN

  • Page 1: Operation Menu

    RH 25 to 85% (10) Make sure the controller has 30 minutes or more for warm up. OMRON shall not be responsible for conformity with any standards, codes, or regulations that Safety Precautions (11) When executing self-tuning, turn the load and the unit ON simultaneously, Storage temperature –25 to 65°C...
  • Page 2 入力が制御可能範囲内で表示可能範囲(–1999(–199.9)∼ 9999(999.9) )を超えた 初期設定レベル 通信設定レベル 高機能設定レベル 設定値 場合、–1999(–199.9)より小さい値は [[[[、9999(999.9)より大きい値は ]]]] ●コマンドフォーマット 絶対値上限 と表示します。 待機シーケンス付 ○ ○ ○ この表示のときは制御出力および警報出力ともに正常に動作します。 CompoWay/Fの場合 ○ ○ × 制御可能範囲についての詳細は「形 E5GN ユーザーズマニュアル」を参照してくださ 絶対値下限 い。 待機シーケンス付 × × × ノード サブア FINS-mini *6:表示が「現在値/目標値」のときだけエラー表示します。他の状態 ドレス コマンドテキスト 工場出荷設定値「1」 ○:移行可能 *1:設定値1、4、5は警報種別の上・下限値が個別に設定でき、 ではエラー表示しません。 ×:移行不可能...