1.4 Communications Function

F Setting up
communications
data
Parameter
Communications unit No.
Baud rate
Data bit
Stop bit
Parity
The E5GN can be provided with a communications function that allows
you to check and set controller parameters on a host computer. If the com
munications function is required, use the model supporting the commu
nications function E5GN j03j. For details on the communications func
tion, see the separate Communications Functions User's Manual."
Follow the procedure below to move to the communication setting level.
(1) Press the
key for at least three seconds in the operation level".
The level moves to the initial setting level".
(2) Press the
key for less than one second. The initial setting level"
moves to the communications setting level".
(3) Pressing the
key advances the parameters as shown in the follow
ing figure.
(4) Press the
or
Set the E5GN communications specifications so that they match the com
munications setup of the host computer. In the case of a one to N connec
tion, match the communications setup of all units.
Symbol
Setting
0 to 99
1.2, 2.4, 4.8, 9.6, 19.2
7, 8
1, 2
None, even, odd
Communications Function
1.4
keys to change the parameter setups.
Communications unit No.
Baud rate
Data bit
Stop bit
Parity
Set value
.
,
.
,
.
,
.
,
,
,
Default
Unit
1
None
.
9.6
kbps
7
Bit
2
Bit
Even
None
1–9