CHAPTER 5 PARAMETERS
Initial Setting Level
Initial Setting Level
_C/_F selection
• Set the temperature input unit to either of _C" or _F".
Function
Setting
F Related parameter
Input type" (initial setting level)
See
Set point upper limit
Set point lower limit
• This parameter limits the upper and lower limits when the SP is set. The SP can be
set within the range defined by the upper and lower limit set values in the set point
upper limit" and set point lower limit" parameters. The existing SP settings that are
Function
out of the range are forcibly changed to one of the upper or lower limit values (which
ever is closest).
• When the temperature input type and temperature unit have been changed, the set
point upper limit and set point lower limit are forcibly changed to the upper and
lower limits of the sensor.
• During temperature input, the decimal point position is dependent on the currently
selected sensor. During analog input, it is dependent on the decimal point" parame
ter setting.
Set point upper limit
Setting
Set point lower limit
F Related parameters
Input type" _C/_F selection" (initial setting level)
See
5–20
Setting Range
: _C / : _F
Parameter
Set point lower limit +1 to sensor range upper limit
Platinum resistance thermometer
Sensor range lower limit to set point upper limit -1
The input type must be set to temperature
input.
Default
Setting Range
Unit
Default
EU
1300
EU
850
EU
-200