Omron E5GN User Manual page 102

Hide thumbs Also See for E5GN:
Table of Contents

Advertisement

Output input error
• When this setting is set to ON", alarm 1 output becomes ON at an input error. Note,
however, that the alarm 1 operation display does not light.
• The alarm 1 output is the ORed output of alarm 1, HBA used and input error.
Function
• Output is turned OFF when the initial setting level, communications setting level,
advanced function setting level or calibration level is switched to.
Setting
F Related parameter
Input error" (error display) (p. A 4)
See
Cold junction
compensation method
• Specifies whether cold junction compensation is to be performed internally by the
controller or to be performed externally when the input type setting value is No.0 to
15, 17 or 18.
Function
• The cold junction compensation external setting is valid when the temperature dif
ference is measured using two thermocouples or two ESIAs.
: internally /
Setting
F Related parameter
Input type" (initial setting level) (p. 5 16)
See
Advanced Function Setting Level
Setting Range
: ON /
: OFF
Setting Range
: externally
The alarm 1 type must be supported.
The control must be set to standard control.
Default
Input type must be thermocouple or non–con-
tact temperature sensor
Default
5–35