JCharacteristics
Indication accuracy
Hysteresis
Proportional band (P)
Integral time (I)
Derivative time (D)
Control period
Manual reset value
Alarm setting range
Sampling period
Insulation resistance
Dielectric strength
Malfunction vibration
Vibration resistance
Malfunction shock
Shock resistance
Weight
Protective structure
Memory protection
*1 The indication of K thermocouples in the 200 to 1300_C range, T and N thermocouples at a temperature of 100_C or less,
and U and L thermocouples at any temperature is ±2_C±1 digit maximum. The indication of B thermocouples at a tempera
ture of 400_C or less is unrestricted.
The indication of R and S thermocouples at a temperature of 200_C or less is ±3_C±1 digit maximum.
Thermocouple:
(±0.5% of indication value or ±1_C, whichever is greater) ±1 digit max. (*1)
Platinum resistance thermometer:
(±0.5% of indication value or ±1_C, whichever is greater) ±1 digit max.
Analog input: ±5%FS±1 digit max.
0.1 to 999.9EU (in units of 0.1EU)
0.1 to 999.9EU (in units of 0.1EU)
0 to 3999 (in units of 1 second)
0 to 3999 (in units of 1 second)
1 to 99 (in units of 1 second)
0.0 to 100.0% (in units of 0.1%)
-1999 to 9999 (decimal point position dependent on input type)
500 ms
20 MΩ min. (by 500 VDC megger)
2000 VAC 50 or 60 Hz 1min
10 to 55 Hz, 10 m/s2 for 10 min. each in X, Y and Z directions
300 10 to 55 Hz, 20 m/s2 for 2 hrs. each in X, Y and Z directions
200 m/s2 max. 3 times each in 3 axes, 6 directions (relay: 100 m/s2)
300 m/s2 max. 3 times each in 3 axes, 6 directions (relay: 100 m/s2)
Approx. 90 g
Adapter: approx. 10g
Front panel: NEMA4X for indoor use (equivalent to IP66),
Rear case: IP20, terminals: IP00
EEPROM (non-volatile memory) (number of writes: 100,000)