CHAPTER 5 PARAMETERS
Operation Level
Set point during SP ramp
This parameter monitors the set point during SP ramp.
Ramp" is a function for restricting the change width of the set point as a change rate.
The set value is displayed when SP ramp set value" parameter (advanced function
setting level) is set.
Function
When the set point is out of the preset ramp, the set point is matched to the set point
set in the PV/SP" parameter.
SP: Set point lower limit to set point upper limit
Monitor
F Related parameters
PV/SP" (operation level)
SP ramp set value" (advanced function setting level)
See
Set point upper limit" Set point lower limit" (initial setting level)
5–6
The "SP ramp set value" parameter must not
be set to "OFF".
Monitor Range
Unit
EU