CHAPTER 4 APPLIED OPERATION
4.1 Shifting Input Values
JShifting input
F 1-point shift
Tempera-
ture input
shift
Operation Procedure
Operation level
Adjustment level
Temperature input
shift
Operation level
4–2
• The input shift type matched to the sensor currently selected in the
input type" parameter is displayed.
• 2 point shift is applied only for non contact temperature sensors.
• With 1 point shift, only the value set to the Temperature input shift"
parameter (adjustment level) is applied to the entire temperature input
range. For example, if the input shift value is set to 1.2_C", the process
value is treated as 201.2_C" after input shift is applied when the pro
cess value is 200_C.
Temperature
Upper-limit
value
After shift
Lower-limit
value
0
In this example, let's shift the input of the K sensor by 1_C" by 1 point
input shift.
Operation level
(1) Press the
key to move from the operation level" to the adjust
ment level".
(2) Select the temperature input shift" parameter by pressing the
key.
(3) Press the
or
(4) To return to the operation level," press the
value 1_C larger than before shift is applied.
Before
shift
Input shift value
100
keys to set 1".
Input
key. The process