11-10-3. Indoor Unit (Other Parts)
No.
Part name
1
Room temp. (TA) sensor
Heat exchanger (TC) sensor
Heat exchanger (TCj) sensor
2
Remote controller
3
Louver motor
(right, left, Horizontal)
MP24Z3N
4
Louver motor (Moving panel)
MP24Z4N
5
Indoor fan motor

11-10-4. Outdoor Unit

No.
Part name
1
Compressor
(Model : DA130A1F-25F)
2
Outdoor fan motor
(Model : ICF-140-43-4R)
3
Compressor thermo. bimetal type
(Model : US-622KXTMQO-SS)
Disconnect the connector and measure the resistance value with tester.
(Normal temp.)
Temperature
Sensor
TA, TC, TCj (k )
Refer to page 82. Troubleshooting for Remote Controller
Measure the resistance value of each winding coil by using the tester.
(Under normal temperature 25°C)
White
1
1
Yellow
2
2
Yellow
3
3
Yellow
4
4
Yellow
5
5
Measure the resistance value of each winding coil by using the tester.
(Under normal temp. 25°C)
White
1
1
Yellow
2
2
Yellow
3
3
Yellow
4
4
Yellow
5
5
Refer to page 80. Only the Indoor Motor Fan Does not Operate.
Refer to page 81.
Indoor Fan Motor Automatically Starts to Spin by Turning on Power Supply.
Measure the resistance value of winding by using the tester.
Red
White
Measure the resistance value of winding by using the tester.
Red
White
Check conduction by using the tester.
– 91 –
Checking procedure
10°C
20°C
20.7
12.6
Position
1 to 2
1 to 3
1 to 4
1 to 5
Position
1 to 2
1 to 3
1 to 4
1 to 5
Checking procedure
Position
Red - White
White - Black
Black- Red
Black
Position
Red - White
White - Black
Black- Red
Black
25°C
30°C
40°C
10.0
7.9
4.5
Resistance value
250 ± 20
Resistance value
200 ± 20
Resistance value
0.68 to 0.78
Under 20°C
Resistance value
20 to 22