Toshiba RAS-M10PKVP-E Service Manual page 77

Split type, indoor & outdoor unit
Hide thumbs Also See for RAS-M10PKVP-E:
Table of Contents

Advertisement

11-4-2. Check Code
1. After servicing, press the START/STOP button to return to the normal mode.
2. After servicing by the check code, turn off breaker of the power supply, and turn on breaker of the power
supply again so that memory in the microcomputer returns the initial status.
However, the check codes are not deleted even if the power supply is turned off because they are stored in
the fi xed memory.
3. After servicing, press [CLR] button under check mode status and then send the check code "7F" to the
indoor unit. The error code stored in memory is cleared.
Block distinction
Check
Block
code
Indoor P.C.
board etc.
Not
displayed
Connecting
cable and
serial signal
Operation of diagnosis function
Check
Cause of operation
code
Short-circuit or
disconnection of the
room temperature
sensor (TA sensor).
Being out of place,
disconnection, short-
circuit, or migration of
heat exchanger sensor
(TC sensor)
Being out of place,
disconnection, short-
circuit, or migration of
heat exchanger sensor
(TCj sensor)
Lock of indoor fan or
trouble on the indoor
fan circuit
Trouble on other indoor
P.C. boards
Return serial signal is
not sent to indoor side
from operation started.
1) Defective wiring of
connecting cable
2) Operation of
compressor thermo
Gas shortage Gas
leak
Table 11-4-1
Air
conditioner
Remarks
status
Operation
Displayed when
continues.
error is detected.
Operation
Displayed when
continues.
error is detected.
Operation
Displayed when
continues.
error is detected.
All off
Displayed when
error is detected.
Operation
Displayed when
continues.
error is detected.
Operation
Flashes when
continues.
trouble is detected
on Return serial
signal, and normal
status when signal
is reset.
– 77 –
Judgment and action
1. Check the room temp. sensor.
2. When the room temp. sensor is
normal, check P.C. board.
1. Check heat exchanger sensor.
2. When heat exchanger sensor is
normal, check P.C. board.
1. Check heat exchanger sensor.
2. When heat exchanger sensor is
normal, check P.C. board.
1. Check the motor.
2. When the motor is normal, check P.C.
board.
Replace P.C. board.
1. When the outdoor unit never operate:
1) Check connecting cable, and
correct if defective wiring.
2) Check 25A fuse of inverter P.C.
board.
3) Check 3.15A fuse of connecting
cable of inverter unit and outdoor
unit.
2. To display [Other] block during
operation, check compressor thermo.
operation and supply gas (check gas
leak also).
3. Unit operates normally during check.
If return serial signal does not stop
between indoor terminal board 2 and
3, replace inverter P.C. board.
If signal stops between indoor
terminal board 2 and 3, replace indoor
P.C. board.