FIELD
TITLE and DATA ENTRIES
Pager 2 Phone No.
*163
Enter up to 20 digits
Pager 2 Characters
*164
Enter up to 16 characters
Pager 2 Report Options
*165
see pager 1 reports, field *162 for entries,
except use zone list 10.
Pager Delay Option for Alarms
*166
0 = none
1 = 1 minute

Miscellaneous System Fields

FIELD
TITLE and DATA ENTRIES
RF REPORTING OPTIONS
*173
0 = none
1 = RF Tamper reports during disarm
2 = RF keyfobs send low battery
3 = RF Tamper reports during disarm and
RF keyfobs send low battery
Tamper Options
*175
Entry 1: 0 = standard tamper detection
1 = detect tamper from bypassed
zones
2 = detect tamper when in Test
mode
3 = detect tamper both when in Test
mode and from bypassed zones
Entry 2: 0 = all users can clear a tamper**
1 = only the installer can clear a
tamper
EXPLANATION
If you enter fewer than 20 digits, exit by pressing [∗]
and next field number. To clear entries from this field,
press ∗163∗.
See field ∗161 for explanation. If fewer than 16
characters, exit by pressing [∗] and next field number.
To clear entries, press ∗164∗.
Enter the types of reports to be sent to pager 2 for each
partition.
This field determines the delay of alarm reports to the
pager. This gives the Central Station enough time to
2 = 2 minutes
verify the alarm report that it received, before the
3 = 3 minutes
dialer attempts to dial the pager.
NOTE: The delay does not reset for new alarms
occurring while an existing pager delay is in progress.
This delay is for ALL pagers in the system.
EXPLANATION
Select desired option.
Select desired options.
Standard Tamper Detection (entry 1 option 0): The
system normally detects tamper faults from devices
equipped with tamper switches (for cover removal
and/or wall removal) while the system is armed or
disarmed. Tamper faults are ignored when a zone is
bypassed or when the system is in Test mode unless
entry 1 options 1, 2, or 3 are selected. Tamper display
is as follows:
Disarmed:
Armed:
** Must be "0" if field *25 entry 2 is set for 1 or 2,
otherwise, only the installer will be able to disarm the
system and clear tamper displays.
Data Field Programming
TAMPER 1xx (or zz)
where 1xx = ECP device address
zz = zone number of faulted device.
TMPR_ARMD
4-15