6164 Keypad Expansion Zones - Honeywell ADEMCO Vista-12C Installation And Setup Manual

Table of Contents

Advertisement

Installation and Setup Guide

6164 Keypad Expansion Zones

1. Connect each keypad to the control's keypad
terminals.
2. Using the keypad's program mode, assign the
keypad a unique keypad address (16-23), and
assign a device address of 08 which provides
expansion zones 17-20.
3. Connect sensors to the keypad's zone
terminals.
4. If using the keypad relay, connect the desired
field wiring to the keypad's relay contact
terminals.
See 6164 Keypad Instructions for other
mounting, wiring, and programming
information.
2-10
Notes
• Each 6164 keypad supports up to 4 wired
expansion EOLR or double-balanced zones
and one relay output.
• Use 2000 ohm end-of-line resistors at the
end of loops connected to the 6164 keypads.
• Enter 6164 keypad program mode by
pressing and holding down both the [1] and
[3] keys within 60 seconds of power up.
• Enable the keypad addresses using data
fields *191-*196 as required.
• Program keypad zones using *56 Menu
mode. Keypad zones 1-4 correspond to the
respective groups of zones shown in the
chart at left, where keypad zone 1 is the
lowest zone number in each group.
OPTIONAL
DOUBLE BALANCED
2K
TAMPER
2K
CONTACTS
TAMPER
2K
CONTACTS
N.O.
C.
N.C.
Z1
Z2
(Z1
(Z3
&
&
Z2)
Z4)
CONVENTIONAL
EOLR
2K
[Y] DATA IN (<)
N.O.
[+] +12VDC IN
[-] GROUND (-
N.C.
[G] DATA OUT
Y +
G
Z4
Z3