Important Installation Highlights (Installer Please Read)

• This system uses addressable keypads and a Zone Expander Module (see table of
addresses in Programming Overview section).
• Keypads must be set for addresses 16-23 (first keypad is address 16, which is different
from previous controls) and programmed in data fields *190-*196.
• Zone Expander Module must be set for specific address (08), based on the zone numbers
used
(see table of addresses in 4219/4229 Expansion Zones section).
• 4204 Relay Module must be set for specific address (13; see Connecting Relay
Modules section).
• 6164 Keypads must be set for two addresses: a keypad address and a zone expander
address (if using the keypad's expansion zones).
• This control will not power-up unless AC mains is connected (will not power-up on
battery alone). However, once the system is powered up, it will operate on battery power
in the event of AC mains loss.
• Relays have two programming menu modes: Use *79 Menu mode to map module
addresses and device (output) numbers. Use *80 Menu mode to define the output
functions (see Output Device Programming section).
• This system supports programmable function keys. Use *57 Menu mode to define the
function keys (see Function Key Programming section).
• This system provides various paging features. Refer to the Programming Overview
section for a summary on pager programming.
Features and Installation Highlights
1-3