Ups System Input; Ups System Output; Table 8-2: Ups System Input - Eaton 93PM User And Installation Manual

30-200 kw ups
Table of Contents

Advertisement

8.2 UPS system input

Rated input voltage
Voltage tolerance, (Rectifier input)
Voltage tolerance, (Bypass input)
Rated input frequency
Frequency tolerance
Number of input phases, (Rectifier input)
Number of input phases, (Bypass input)
Input power factor
Rated mains input current
Maximum mains input current
Input current distortion at rated input current,
iTHD
Rectifier ramp-up, rectifier start and load step
Backfeed protection

Table 8-2: UPS system input

8.3 UPS system output

Number of output phases
Rated output voltage
P-164000249
Revision 2
220/380 V; 230/400 V; 240/415 V
230 V -15 % / +20 %
230 V -15 % / +10 %
50 or 60 Hz, user configurable
40 to 72 Hz
3 phases + N
3 phases + N
0,99
See Table 3-7: Rated and maximum currents for
rated power and voltage on page 31
30 kW: < 4,5 %
40-200 kW: < 3 %
10 A/s (default), configurable. Min 1A/s
Yes, for rectifier and bypass lines
3 phases + N
220/380 V; 230/400 V; 240/415 V, configurable
30-200 kW
User's and Installation Guide
77