Table 3-6: Minimum Recommended Multi-Core Cable And Fuse Sizes - Eaton 93PM User And Installation Manual

30-200 kw ups
Table of Contents

Advertisement

• The bypass feed into this equipment uses four wires. The rectifier feed into this equipment uses
three or four wires. The phases must be symmetrical about ground (from a Wye source) for
proper equipment operation.
• If the load requires a neutral, a bypass source neutral must be provided. If the load does not
require a neutral and there is no neutral conductor connected at the bypass input, a neutral must
be installed to source star point.
• A readily accessible disconnect device must be incorporated in all fixed input wiring.
Rectifier input
UPS
rating
Fuse
50 kW
3x 100
A
-
50 kW
Maximum
100 kW
3x 200
A
150 kW
3x 315
A
200 kW
3x 400
A

Table 3-6: Minimum recommended multi-core cable and fuse sizes

Rated
Rated
power
voltage
30 kW
380 V
400 V
415 V
40 kW
380 V
400 V
415 V
50 kW
380 V
P-164000249
Revision 2
Bypass input
Cable
Fuse
4x 35
3x 100
mm²
A
4x 50
-
mm²
4x 70
3x 200
mm²
A
4x 150
3x 315
mm²
A
4x 240
3x 400
mm²
A
Rectifier
Rectifier
input
input
Rated
Max.
current
current
48
57
46
54
44
52
64
76
61
72
58
69
80
95
30-200 kW
User's and Installation Guide
PE
UPS
output
(380/400/
415V)
Cable
Cable
Cable
4x 35
4x 35
35 mm²
mm²
mm²
4x 50
4x 50
35 mm²
mm²
mm²
4x 70
4x 70
35 mm²
mm²
mm²
4x 150
4x 150
95 mm²
mm²
mm²
4x 240
4x 240
120
mm²
mm²
mm²
UPS
UPS
Output/
Output/
Bypass
Bypass
Rated
Max.
current
current
46
55
44
52
42
50
62
73
59
70
56
66
77
91
Battery
Fuse
Cable
200 A
2x 70
mm²
-
2x 95
mm²
400 A
2x 150
mm²
500 A
4x 150
mm²
630 A
4x 240
mm²
Battery
Battery
Rated
Max.
current
current
73
95
73
95
73
95
97
126
97
126
97
126
121
158
31