Figure 5-4: Relay Card-MS

• Network and MODBUS Card - MS
Provides remote monitoring through a Web browser interface, e-mail, and a network
management system (NMS) using SNMP and connects to a twisted-pair Ethernet (10/100BaseT)
network. The card also provides direct integration of UPS information (meters and status) to a
Building Management System (BMS) using the Modbus RTU protocol.

Figure 5-5: Network and MODBUS Card - MS

• Industrial Relay Card-MS
The Mini-Slot Industrial Relay Card provides a way of connecting the 93PM to industrial and
electrical monitoring systems. It also enables a wide range of control applications by allowing
up to 250 volts and 5 Amperes through its 5 relay connections. By connecting wires to the
corresponding places in its terminal blocks you can choose Normally Open or Normally Closed
setup for each output.