Battery System Installation; Figure 4-4: 93Pm 30-150 Kw Top Cable Access Kit - Eaton 93PM User And Installation Manual

30-200 kw ups
Table of Contents

Advertisement

Figure 4-4: 93PM 30-150 kW Top cable access kit

4.2 Battery system installation

This UPS may have internal batteries. Connection of these batteries is to be left to the responsibility
of the commissioning personnel in order to avoid damages to the equipment or personal injuries in
case of an incorrect connection. The batteries are designed to deliver a large amount of energy and an
incorrect connection may lead to short circuit and cause serious injuries to the personnel or damages
to the equipment.
If installing a customer-supplied battery system, install the battery system according to the battery
and battery system manufacturer's instructions and all applicable national codes and regulations. Only
qualified personnel may install the battery system. Battery cables must be protected against current
and thermal overload, that is, the battery system must include proper fuses or breaker with protection
function.
The default battery settings of the UPS are for 12 VDC VRLA batteries. If requested to use other
battery types, contact your Eaton representative. For the battery specification, see Chapter 8.4
Battery specification on page 78.
40
30-200 kW
P-164000249
User's and Installation Guide
Revision 2