8.2

UPS System Input

Table 8-2: UPS System Input
Rated Input Voltage
Voltage Tolerance, (Rectifier Input)
Voltage Tolerance, (Bypass Input)
Rated Input Frequency
Frequency Tolerance
Number of Input Phases, (Rectifier Input)
Number of Input Phases, (Bypass Input)
Input Power Factor
Rated Mains Input Current
Maximum Mains Input Current
Input Current Distortion at Rated Input Current,
iTHd
Rectifier Ramp-up, Rectifier Start and Load Step
Backfeed Protection
220/380 V; 230/400 V; 240/415 V
Rated input voltage -15 % / +20 %
Rated input voltage -10 % / +10 %
50 or 60 Hz, user configurable
40 to 72 Hz
3 phases + N
0,99
See Table 3-7: Rated and maximum currents for rated
power and voltage on page 31
< 3 %
5 A/s per UPM (default), configurable. Min 1A/s per
UPM
Yes, for rectifier and bypass lines
25-75 kW
User's and Installation Guide
80