Technical Data; Model Numbers; Ups System Input - Eaton 93E G2 100/100 User And Installation Manual

Table of Contents

Advertisement

Eaton 93E Generation 2 UPS 100-200 kVA
(380/400/415V)
9

Technical data

For a complete technical specification, contact your Eaton representative. Due
to continuous product improvement programs, specifications are subject to
change without notice.
9.1
The UPS is housed in a free-standing cabinet with safety shields behind the
door. The UPS is available in 50 or 60 Hz with various output power ratings.
Table 23: Model numbers
Models
Eaton 93E G2 100/100
Eaton 93E G2 120/120
Eaton 93E G2 200/160
Eaton 93E G2 200/200
9.2
Table 24: UPS input
Item
Number of input phases (rectifier & bypass) 3 phases + N
Operating input voltage
Input voltage range
Operating input frequency range
Input frequency range
Operating input current
Input current distortion, iTHD
Power factor
Back feed protection
Line surges
Table 25: Battery specification
Item
Battery voltage
©
Eaton Corporation plc 2019. All rights reserved.

Model numbers

Power rating
100 kVA
120 kVA
160 kVA
200 kVA

UPS system input

Value
380/400/415 Vac
196/330–276/478V at 100% load
126/201-276/478V at 50% load
50/60 Hz
40-72 Hz
11
See Table
< 3% at load range 80% to 100%
> 0.99 at rated load
Yes, for rectifier and bypass lines
6 kV OC, 3 kA SC per ANSI 62.41 and IEC
801 4
Value
432 VDC (36 blocks), 456 VDC (38 blocks)
or 480 VDC (40 blocks)
Revision: 002
Document ID: P-164000848
User's and installation guide
Frequency
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
.
107 (118)