Ups Environmental Specifications; Table 8-4: Battery Specification - Eaton 93PM User And Installation Manual

30-200 kw ups
Table of Contents

Advertisement

Battery quantity
Battery voltage
Recharge profile
End of discharge voltage
Charge current
30-50 kW units
80-100 kW units
120-150 kW units
160-200 kW units
Battery start option

Table 8-4: Battery specification

Note! For external battery connection, 24 VDC Shunt Trip signal wiring from the UPS must be
connected to the auxiliary signal connection of the battery breaker.

8.5 UPS environmental specifications

Acoustic noise at 1 m
Ambient UPS storage temperature range
P-164000249
Revision 2
30-50 kW units: 36 blocks, 216 cells per battery string
80-200 kW units: 36 blocks, 216 cells per battery string, or 40
blocks, 240 cells per battery string
Note! Battery strings with different battery quantity and voltage may not
be connected in parallel!
432 V (36 blocks) or 480 V (40 blocks)
ABM or float charge
1.67 VPC to 1.75 VPC, configurable or automatic (load adaptive)
Configurable:
Default 12 A, max 22 A (common for internal and external batteries
Default 24 A, max 44 A
Default 36 A, max 66 A
Default 48 A, max 88 A
Yes
30-50 kW: <60 dBA
80-200 kW: <65 dBA
ESS operation: <45 dBA
From -25 °C to +55 °C in the protective
package*
30-200 kW
User's and Installation Guide
79