Figure 5-6: Industrial Relay Card-MS

5.2 Intelligent Power Software

Intelligent Power Software are productivity tools for UPS power management. The Intelligent
Power Protector (IPP) application provides automatic, graceful shutdown of computers and virtual
machines or servers powered by an Eaton UPS during a power outage that lasts longer than your
available battery runtime. Intelligent Power Protector can be remotely supervised and managed by the
Intelligent Power Manager (IPM) application. The IPM delivers a global view of power devices across
the network from any PC with an Internet browser. The software enables single, Web-based interface
for remote monitoring and management of Eaton and other manufacturers' UPSs, environmental
sensors and Power Distribution Units (ePDU) products, even in virtualized environments.
The Intelligent Power Software is delivered on a CD with the UPS. Alternatively, you can download it
from the Eaton web page.

5.3 Signal input monitoring

This standard feature lets you connect the UPS to your signal inputs, such as smoke detectors or
overtemperature alarms. The customer interface terminals for external connections are located inside
the UPS. You should use twisted-pair wires for each alarm input and common.
The signal inputs can be programmed to display the alarm functional name.

5.4 General purpose relay contact

One general purpose relay contact is provided as a standard feature on the UPS. An alarm contact is
also provided.
You can use a normally-closed or normally-open contact. If the state of the contact changes from
the state you specify as normal, a signal is issued. You can connect this contact to equipment at
your facility (such as a light or an alarm bell) to let you know when an alarm is active on the UPS.
This feature is useful if the UPS is located in a remote area where the UPS horn may not be heard
immediately.