Table 3-5: Air Conditioning Or Ventilation Requirements During Full Load Operation - Eaton 93PM User And Installation Manual

30-200 kw ups
Table of Contents

Advertisement

Rating
30 kW
40 kW
50 kW
80 kW
100 kW
120 kW
150 kW
160 kW
200 kW

Table 3-5: Air conditioning or ventilation requirements during full load operation

Figure 3-2: 93PM 30-150 kW UPS dimensions
28
Heat rejection (BTU/h x 1000)
4.30
5.73
7.16
11.45
14.32
17.18
21.48
22.91
28.64
30-200 kW
User's and Installation Guide
Heat rejection (kW)
1.3
1.7
2.1
3.4
4.2
5.0
6.3
6.7
8.4
P-164000249