Figure 3-1: Ups Cabinet Clearances. See Table 3-3; Table 3-4: Ups Cabinet Minimum Clearances With Top Air Exhaust Kit - Eaton 93PM User And Installation Manual

30-200 kw ups
Table of Contents

Advertisement

From top of cabinet
From front of cabinet
From back of cabinet

Table 3-4: UPS cabinet minimum clearances with top air exhaust kit

• X = clearance at back of cabinet
• Y = clearance at top of cabinet

Figure 3-1: UPS cabinet clearances. See Table 3-3.

The basic environmental requirements for operation of the UPS system are:
• Ambient Temperature Range: from +5 to +40 °C
• Recommended Operating Range: from +20 to +25 °C
• Maximum Relative Humidity: 95 %, noncondensing
It is required to arrange ventilation of the UPS room. Sufficient amount of air cooling is needed to
keep the maximum room temperature rise at desired level:
• Temperature rise of max. +5 °C requires the airflow of 600 m³ per 1 kW of losses
• Temperature rise of max. +10 °C requires the airflow of 300 m³ per 1 kW of losses
An ambient temperature from +20 to +25 °C is recommended to achieve a long life of the UPS and
batteries. The cooling air entering the UPS must not exceed +40 °C. Avoid high ambient temperature,
moisture, and humidity.
The UPS ventilation requirements are shown in the following table:
P-164000249
Revision 2
30-50 kW
500 mm
900 mm
0 mm
30-200 kW
User's and Installation Guide
80-200 kW
800 mm
900 mm
0 mm
27