Total voltage harmonic distortion
100 % linear load
100 % non-linear load
Rated output frequency
Output frequency variation
Slew rate
Overload capability at ambient 40 °C
(On inverter)
Overload capability at ambient 40 °C
(On inverter, stored energy mode)
Overload capability at ambient 40 °C
(On bypass)
Output current
Load power factor, (Rated)
Load power factor, (Permitted range)

Table 8-3: UPS system output

8.4 Battery specification

Battery type
78
< 1 %
< 5 %
50 or 60 Hz, configurable
± 0,1 Hz
1 Hz/s
10 min 102-110 % load
60 sec 111-125 % load
10 sec 126-150 % load
300 ms > 150 % load
10 min 102-110 % load
60 sec 111-125 % load
300 ms > 126 % load
Continuous < 125 % load
10 ms 1000 % load
Note! Bypass fuses may limit the overload capability.
See Table 3-7: Rated and maximum currents for rated
power and voltage on page 31
1.0
From 0.8 lagging to 0.8 leading
VRLA, 12 VCD
30-200 kW
User's and Installation Guide
P-164000249
Revision 2