4-6 Description of the auto battery test function

This UPS provides functions to automatically check whether replacing the battery is required and whether the
internal circuit is at fault. (You do not have to perform any operation.)
The test is performed at intervals of 4 weeks after the AC Input Plug is connected to a wall outlet (commercial
power). If you disconnect the AC Input Plug from a wall outlet (commercial power) when the Power Switch of
the UPS is OFF, the 4-week timer is reset. If the Power Switch is OFF, the test is not performed.
(1) When the auto battery test starts, the Battery Mode automatically starts. (No beep sounds.) After the auto
battery test is complete, the normal operation automatically starts.
(2) If the Alarm Lamp blinks and the beeper sounds:
"4-3 Interpreting a beep and display" ➛ Page 21
See also
Take necessary countermeasures according to the remedy in "4. Display and beep when a failure occurs
in equipment." or "5.Display and beep when battery replace."
The setting switch on the rear of the UPS allows you to select the "disable the auto battery test" setting.
"4-7 Changing the setting of the functions" ➛ Page 23
See also
See "●Auto battery test ON/OFF setting."

4-7 Changing the setting of the functions

1. Selecting functions with the setting switches
After changing the setting switches, turn on the Power Switch again.
Operation
• Otherwise, the change will not take effect.
● Power output stop delay time setting (setting switches 1 and 2 ) ... Factory-
shipped setting: ON and ON
When the UPS Stop Signal is received, the UPS stops after a specified time period has elapsed.
(1) When you perform shutdown processing for Windows ME using "PowerCredit" the UPS monitoring
software you can purchase separately, set the delay time.
When performing the auto shutdown processing by the UPS monitoring software ➛ Page 37
See also
(2) When you perform shutdown processing using the UPS management software of Windows NT or using
"PowerCredit" the UPS monitoring software for Windows 98/95, set the switches to ON and OFF (no
delay time).
When performing the auto shutdown processing by WindowsNT's UPS management software
See also
➛ Page 39
When performing the auto shutdown processing by the UPS monitoring software
See also
➛ Page 37
23
4. Operation