Description Of The Auto Battery Test Function; Changing The Setting Of The Functions - Omron POWLI Instruction Manual

Table of Contents

Advertisement

4-3

Description of the auto battery test function

This test performs a failure diagnosis on the unit and performs a test to check for battery deterioration.
(This test is more accurate than the self-diagnostic test.)
This test is performed automatically. (You do not have to perform any special operations.)
The test is performed at intervals of 4 weeks after the AC Input Plug is connected to a wall outlet (commercial
power).
The test is not performed if the power switch is OFF or if the battery is not fully charged.
(1) When the auto battery test starts, the Battery Mode automatically starts (Status indicator "
beep sounds.) After the auto battery test is complete, the normal operation automatically starts.
(2) If the status indicator/battery replacement lamp blinks and the beeper sounds:
"3-3 Interpreting beeps and displays" ➛ Page 30
See also
Follow the directions for the solutions described in "4. Displays and beeps when there is an equipment
failure" and "5. Display and beep for battery replacement".
The setting switch on the Front of the UPS allows you to select the "disable the auto battery test" setting.
"4-4 Changing the setting of the functions" ➛ Page 33
See also
See "Setting for whether or not to perform battery test"
This test can also be performed manually.
Press and hold the Beep Stop/Test Switch of the UPS for 10 second or longer.
When the beeper changes from intermittent beeps to a sustained beep, release the switch.
4-4

Changing the setting of the functions

1. Selecting functions with the DIP switch
After changing the setting switch, follow the procedure described below.
After changing the setting switch, turn OFF the UPS power siwtch, disconnect
the AC input plug, wait until the status indicator is completely OFF, and then
reinsert the AC input plug.
● The setting switch changes do not become valid until the AC input plug is reinserted.
• Use a fine-pointed tool such as a small screwdriver to maneuver the switch's lever.
STATUS
LOAD/
BATTERY
POWER ON/OFF
BEEP STOP/TEST
OUTPUT
BATTERY
BYPASS
WEAK
1002
3002
BU
SWG / BU
SWG
"). (No
4
33

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bu3002swgBu1002swg

Table of Contents