Top Vent Configuration with Vertical Termination

Use 6-5/8" Diameter Vent
Horizontal sections require a ¼" (6mm) rise every 12" (305mm) of travel.
A maximum of four (4) 45° or 90° elbows may be used. Of these elbows, only one (1) may be a
horizontal elbow (see illustration).
The termination must fall within the shaded area shown in the chart. Use the indicated restrictor
positions. NOTE: Restrictor positions are based upon lab tests. The ideal restrictor position may
vary slightly, especially when the termination is near a demarcation line.
Diffuser set to open (stock) position.
Install the intake damper plate.
Install the exhaust restrictor extender plate.
© Travis Industries
Installation
(for qualified installers only)
4121120
100-01315