Horizontal Vent Termination Requirements (see the illustration below)
A
Minimum 9" (225 mm) clearance from any door or window
B
Minimum 12" (300 mm) above any grade, veranda, porch, deck or balcony
C
Minimum 12" (300 mm) from outside corner walls
D
Minimum 12" (300 mm) from inside corner walls
E
Minimum 11" (275 mm) clearance below unventilated soffits or roof surfaces
Minimum 18" (450 mm) clearance below ventilated soffits
Minimum 6" (150 mm) clearance from roof eaves
NOTE: Vinyl surfaces require 24" (600 mm)
F
Minimum 18" (450 mm) clearance below a veranda, porch, deck or balcony (must have two open sides)
G
Minimum 48" (1220 mm) clearance from any adjacent building
H
Minimum 84" (2130 mm) clearance above any grade when adjacent to public walkways or driveways
NOTE: may not be used over a walkway or driveway shared by an adjacent building
I
Minimum 48" (1220 mm) clearance from any mechanical air supply inlet, 72" (1820 mm) for Canada
J
Minimum 36" (910 mm) clearance above and 48" (1220 mm) below and to the sides of non-mechanical air supply inlet
K
Minimum 36" (910 mm) from the area above the meter/regulator (vent outlet)
L
Minimum 36" (910 mm) from the meter/regulator (vent outlet)
G
NOTE: Measure clearances to the nearest edge of the exhaust hood.
¥
Use the vinyl siding standoff (#950) when installing on an exterior with vinyl siding.
¥
Vent termination must not be located where it will become plugged by snow or other material
¥
These clearances meet UMC-1994 and the CNA/CGA-B149 code standards
Vertical Vent Termination Requirements (see the illustration below)
Use the vertical
termination (Part #991)
Use the
chart to the
right to
determine
the required
vent
termination
height.

Electrical Connection

¥
Plug the power cord into a grounded 120 Volt outlet (do not remove the grounding plug).
I
TOVE
NSTALLATION
A
F
D
Height
Roof
Pitch
(C
.) -
ONT
For qualified installers only!
E
K
I
C
L
B
Roof Pitch
Minimum Height*
Flat to 6/12
6/12 to 8/12
1.5' (.45 M)*
8/12 to 9/12
9/12 to 10/12
2.5' (.75 M)
10/12 to 11/12
3.25' (1 M)
11/12 to 12/12
12/12 to 14/12
14/12 to 16/12
16/12 to 18/12
7' (2.15 M)
18/12 to 20/12
7.5' (2.25 M)
20/12 or greater
8' (2.45 M)
Roof
Surface
11Ó Min.
6Ó Min.
E
A
J
H
1' (.3 M)*
* In Canada the
2' (.6 M)
vent termination
must be a
minimum 2' (.6 M)
4' (1.2 M)
tall and 2' (.6 M)
5' (1.5 M
above any portion
6' (1.8 M)
of the roof within
10' (3 M) of the
vent.
P
13
AGE
Roof
Eaves