Mitsubishi Electric MELSEC Q Series User Manual page 102

Programmable controller multiple cpu system
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

(c) When using the Universal model QCPU
Product
CC-Link IE controller network
*5
module
Q series MELSECNET/H
network module
Q series Ethernet interface
module
Q series CC-Link system
master/local module
Interruption module
GOT
*1: One CPU module with CC-Link network parameter setting in GX Developer can control the following number of the CC-Link master/local
modules.
• Q00UCPU, Q01UCPU, Q02UCPU: up to 4
• Except Q00UCPU, Q01UCPU, Q02UCPU: up to 8
There is no restriction on the number of mountable modules when setting parameters with the CC-Link dedicated instructions.
CC-Link Master/Local Module User's Manual
*2: For the model name of the applicable GOT, refer to the following manual.
GOT1000 Series Connection System Manual
*3: The number of interrupt modules where the interrupt pointer setting is not made is shown.
If set, there is no restriction on the number of mountable modules.
*4: The number of mountable modules per QCPU, Q00UCPU, Q01UCPU, or Q02UCPU, are limited as shown below.
• Q02UCPU: up to two
• Q00UCPU or Q01UCPU: up to one
*5: When the following CPU module is used in a multiple CPU system configuration, "Number of mountable modules per system" and
"Number of mountable modules per CPU" for CC-Link IE controller network modules are up to two respectively.
• High Performance model QCPU
• Process CPU
*6: The number of mountable modules per QCPU, Q00UCPU, Q01UCPU, or Q02UCPU, and per system are limited as shown below.
• Q02UCPU: up to two
• Q00UCPU or Q01UCPU: up to one
*7: Applicable to the function version B or later.
Table2.23 Modules of restricted quantity
Model
• QJ71GP21-SX
• QJ71GP21S-SX
• QJ71LP21
• QJ71BR11
• QJ71LP21-25
• QJ71LP21S-25
• QJ71LP21G
• QJ71LP21GE
• QJ71NT11B
• QJ71E71
• QJ71E71-B2
• QJ71E71-B5
• QJ71E71-100
• QJ61BT11N
• QI60
• GOT1000 series (Bus
*2
connection only)
CHAPTER2 SYSTEM CONFIGURATION
Number of modules that
can be mounted per
system
Up to 4 modules
*6
Up to 4 modules
*1,*7
No restriction
*3
Up to 4 modules
Up to 5 modules
Quantity restriction per
QCPU
*4
Up to 4 modules
*6
Up to 4 modules
*1,*7
No restriction
*3
Only 1 module
Up to 5 modules
2 - 54
1
2
3
4
5
6
7
8

Advertisement

Table of Contents
loading