Omron CP1E Series User Manual page 143

Cp1e cpu unit hardware
Table of Contents

Advertisement

Reference
Error flag
Error code (A400)
Error information
Cycle Time Exceeded Error
Cause
This error occurs when the cycle time
PV exceeds the maximum cycle time
set in the PLC Setup.
Reference
Error flag
Error code (A400)
Error information
Errors Created with FALS Instructions
Cause
FALS instruction executed
(fatal error) in the program.
Reference
Error flag
Error code (A400)
Error information
CP1E CPU Unit Hardware User's Manual(W479)
Program Error Flag, A401.09
80F0
Program Error Details, A294 to A299
• Change the program to reduce the cycle time.
• Change the maximum cycle time setting.
• Refer to the Maximum Interrupt Task Processing Time (A440) and
study the maximum cycle time.
For example, use the JUMP instruction to skip sections that are not
executed to shorten the cycle time.
Cycle Time Too Long Error, A401.08
809F
C100 hex will be added to the FALS number (001 to 1FF hex) and the result will
be stored in A400 as the error code (C100 to C2FF hex).
Check the conditions for executing FALS instructions and remove any causes
for the user-defined error.
FALS Error Flag, A401.06
C101 to C2FF
6 Troubleshooting
Remedy
Remedy
6
6-11