Wiring For Serial Communications; A-4-1 Recommended Rs-232C Wiring - Omron CP1E Series User Manual

Cp1e cpu unit hardware
Table of Contents

Advertisement

A-4

Wiring for Serial Communications

This method can be used only with a CP1E N-type CPU Unit.
A-4-1
Recommended RS-232C Wiring
Recommended RS-232C Wiring
We recommend the following wiring method for the RS-232C, especially in environments prone to
noise.
1
Use shielded twisted-pair cables for the communications cables.
• Recommended RS-232C Cables
UL2464 AWG28x5P IFS-RVV-SB (UL product)
AWG28x5P IFVV-SB (non-UL product)
UL2464-SB (MA) 5Px28AWG (7/0.127) (UL product)
CO-MA-VV-SB 5Px28AWG (7/0.127) (non-UL product)
2
Combine a signal wire and SG (signal ground) wire in a twisted-pair cable.
At the same time, bundle the SG wires at the connectors on Option Board and the remote
device.
3
Connect the shield of the communications cable to the hood (FG) of the RS-232C connector on
the Option Board.
At the same time, ground the ground terminal (GR) of the CPU Unit to 100 Ω or less.
Connection Example
Example: Twisted-pair Cable Connecting SD-SG, and RD-SG Terminals in Host Link Mode
CPU Unit
Signal
FG
SD
RS-232C
RD
interface
RS
CS
5V
DR
ER
SG
D-sub, 9-pin connector (male)
CP1E CPU Unit Hardware User's Manual(W479)
Model numbers
DOS/V computer
Pin
Pin
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
D-sub, 9-pin connector (female)
Signal
CD
RD
RS-232C
SD
interface
ER
SG
DR
RS
CS
CI
XM2S-0911-E
Appendices
Manufacturer
Fujikura Ltd.
Hitachi Cable,
Ltd.
SG signal wires
Bundle the SG wires
Aluminum foil
A-33

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents