(2) Rotary Switch Setting
Set the temperature range according to the type of temperature sensor
connected to the Unit.
Temperature data will not be converted correctly if the temperature range
does not match the sensor.
Do not set the temperature range to any values other than those for
which temperature ranges are given in the following table.
An incorrect setting may cause operating errors.
The rotary switch is used to set the temperature range.
3
Connect Temperature Sensors.
(1) Thermocouples
(a) CP1W-TS001
CP1E CPU Unit Hardware User's Manual(W479)
9 Using Expansion Units and Expansion I/O Units
CP1W-TS001/TS002
Set-
Input
ting
type
0
K
-200 to 1,300
1
0.0 to 500.0
2
J
-100 to 850
3
0.0 to 400.0
4 to F
Cannot be set.
Either K or J thermocouples can be connected to the CP1W-TS001, but both of the
thermocouples must be of the same type and the same input range must be used for
each.
Input 0
+
Input 0
Temperature input 0
Temperature input 1
WARNIN
Range (°C)
Range (°F)
-300 to 2,300
0.0 to 900.0
-100 to 1,500
0.0 to 750.0
Input 1
NC
+
Input 1
NC
NC
NC
Cold junction compensator
CP1W-TS101/TS102
Input
Range (°C)
Range (°F)
type
Pt100
-200 .0 to
-300 .0 to
650.0
1,200.0
JPt100
-200 .0 to
-300 .0 to
650.0
1,200.0
Cannot be set.
NC
NC
NC
NC
9
9-37