Power Connections

Power Connections
The 301C requires a power range of 17-27 Vac, 50/60 Hz (8.64 VA),
18-36 Vdc, 350 mA @24 Vdc (8.4 VA). Polarization is not important in
either AC or DC mode. The system must be grounded on the
transformer and a dedicated circuit breaker must be used.

Communication Connections

Communication cables must be grounded using the shield terminal,
using twisted and shielded pair Belden 2-24 AWG #9841 cable (or
equivalent).
The network cabling can extend up to a limit of 2000 feet (609 m) per
channel.
The length of a T-tap can reach 65 feet (20 m), up to a maximum of 130
feet (40 m) for all T-taps.
All wireless devices associated to the controller will automatically be
detected and communicate with the controller using wireless
communication protocols.

Settings for Specific Transmitters

Honeywell Sensepoint XCD Transmitters must be configured for 9600
baud, no parity, and a unique address. Honeywell XNX Universal
Transmitters must be configured for 9600 baud and a unique address.
Information on configuring each transmitter is in the associated
technical manual.
16
301C User Manual
M-510324
Honeywell
7/10