Toshiba RemoteEye II User Manual page 93

Table of Contents

Advertisement

23
.../upsAlarmSh
utdownImminen
t
24
.../upsAlarmTe
stInProgress
25
.../upsAlarmPh
aseRotation
26
.../upsAlarmRe
placeBattSoon
27
.../upsAlarmAs
yncOperation
28
.../upsAlarmInp
utOverCurrent
29
.../upsAlarmDC
OverCurrent
30
.../upsAlarmDC
OverVoltage
31
.../upsAlarmDC
UnderVoltage
32
.../upsAlarmOu
tputUnderVolta
ge
The UPS output will be
shutdown in less than 30
seconds due to previously
issued shutdown command.
A UPS battery test is in
progress.
Input phase rotation is
incorrect. Check input wiring
for clockwise rotation.
Batteries nearing end of
expected lifetime. Contact
Toshiba authorized service
center for replacement.
Inverter can not sync to input.
UPS cannot switch from Run
to Stop until input frequency
stabilizes.
UPS reporting Input
Overcurrent. Contact Toshiba
authorized service center for
examination of fault.
UPS reporting DC bus
Overcurrent. Contact Toshiba
authorized service center for
examination of fault.
UPS reporting DC bus
Overvoltage. Contact Toshiba
authorized service center for
examination of fault.
UPS reporting DC bus
Undervoltage. Contact
Toshiba authorized service
center for examination of
fault.
UPS reporting output
Undervoltage. Contact
Toshiba authorized service
center for examination of
fault.
N/A
Battery test completed.
Input phase rotation has been
corrected.
Battery lifetime monitor has been
reset.
N/A
The cause of the Input Overcurrent
condition has been removed. The
UPS is no longer in a INOC fault
mode.
The cause of the DC bus
overcurrent condition has been
removed. The UPS is no longer at
fault.
The cause of the DC bus
overvoltage condition has been
removed. The UPS is no longer at
fault.
The cause of the DC bus
undervoltage condition has been
removed. The UPS is no longer at
fault.
The cause of the output
undervoltage has been removed.
The UPS is no longer at fault.
93