Trane Precedent RT-PRC005 User Manual page 58

Packaged cooling with electric heat rooftop units 3 - 10 tons - 60 hz
Table of Contents

Advertisement

Table ED-9 — Unit Wiring With Electric Heat (Single Point Connection) — 575 Volts — High Efficiency
To Use
Heater
Tons
With
Model No.
BAYHTRRW06A
3
THC036AW
BAYHTRRW12A
BAYHTRRW18A
BAYHTRRW06A
4
THC048AW
BAYHTRRW18A
BAYHTRRW06A
BAYHTRRW12A
5
THC060AW
BAYHTRRW18A
BAYHTRRW23A
BAYHTRSW09A
6
THC072AW
BAYHTRSW18A
BAYHTRSW27A
BAYHTRSW36A
BAYHTRTW18A
THC092AW
BAYHTRTW36A
BAYHTRTW18A
THC102AW
BAYHTRTW36A
BAYHTRTW18A
10
THC120AW
BAYHTRTW36A
BAYHTRTW54A
NOTES:
1. Heater kW ratings are at 208/240 for 208/230V unit
2. HACR type circuit breaker per NEC.
58
Electrical
Data
Heater
kW Rating
1
575 Volts Three Phase
6.0
12.0
17.4
6.0
BAYHTRRW12A
12.0
17.4
6.0
12.0
17.4
23.0
9.0
18.0
27.0
36.0
18.0
BAYHTRTW27A
27.0
36.0
18.0
BAYHTRTW27A
27.0
36.0
18.0
BAYHTRTW27A
27.0
36.0
54.0
Standard Indoor Motor
Control
Max Fuse Size Or
Stages
MCA
Max Circuit Breaker
1
8.6
2
15.8
2
22.3
1
9.1
2
16.3
2
22.8
1
11.8
2
17.1
2
23.6
2
30.3
1
13.5
1
23.8
2
34.6
2
45.4
1
24.8
2
35.6
2
46.4
1
24.8
2
35.6
2
46.4
1
26.3
2
37.1
2
47.9
2
56.6
(High Efficiency)
Oversize Indoor Motor
Max Fuse Size Or
2
MCA
Max Circuit Breaker
15
9.3
20
16.6
25
23.1
15
10.1
20
17.3
25
23.8
15
12.4
20
17.8
25
24.3
35
31.0
20
14.3
25
24.8
35
35.6
50
46.4
25
26.3
40
37.1
50
47.9
25
26.3
40
37.1
50
47.9
30
28.4
40
39.3
50
50.0
60
58.8
2
15
20
25
15
20
25
15
20
25
35
20
25
40
50
30
40
50
30
40
50
30
40
50
60
RT -PRC005-EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents