" " A A " " a a n n d d l l a a t t e e r r d d e e s s i i g g n n s s e e q q u u e e n n c c e e
R R A A *20, *25, *30, *40, *50, *55, *60,
*70, *75
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning
equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person
could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that
are attached to the equipment.
August 2020
S S A A F F E E T T Y Y W W A A R R N N I I N N G G
R R T T - - S S V V X X 0 0 6 6 3 3 E E - - E E N N
Commercial 27 1/2 to 50 ton 60 hz commercial 23 to 42 ton 50 hz cv or vav rooftop air conditioners with reliatel controls (80 pages)
Summary of Contents for Trane IntelliPak RA 20
Page 1
Installation, Operation, and Maintenance IntelliPak™ ™ with Symbio™ ™ 800 Commercial Rooftop Air Conditioners “ “ A A ” ” a a n n d d l l a a t t e e r r d d e e s s i i g g n n s s e e q q u u e e n n c c e e R R A A *20, *25, *30, *40, *50, *55, *60, *70, *75 S S A A F F E E T T Y Y W W A A R R N N I I N N G G...
Page 2
A A L L W W A A Y Y S S r r e e f f e e r r t t o o a a p p p p r r o o p p r r i i a a t t e e S S a a f f e e t t y y D D a a t t a a impact to the environment. Trane advocates the...
Page 3
This document and the information in it are the p p o o l l i i c c i i e e s s . . property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane •...
Voltage Supply ..... . 30 Trane Startup Checklist ....62 Electrical Data .
Page 5
T T a a b b l l e e o o f f C C o o n n t t e e n n t t s s Stop/Off/Auto ......65 Space Static Pressure Control with Statitrac .
Page 6
T T a a b b l l e e o o f f C C o o n n t t e e n n t t s s Superheat High Limit Detection ..80 Ventilation Override .
Page 7
T T a a b b l l e e o o f f C C o o n n t t e e n n t t s s VFD Programming Parameters Final Process ......134 (Supply/Condenser for Low Ambient Wiring Diagrams .
Model Number Description Digit 1 — Unit Type Digit 10, 11— Design Sequence Digit 19 — Relief Fan Motor R = Packaged Rooftop AA = Current Design Sequence 0 = None 2 = 6 hp 3 = 8 hp Digit 2 — Unit Function Digit 12 —...
Page 9
M M o o d d e e l l N N u u m m b b e e r r D D e e s s c c r r i i p p t t i i o o n n Digit 27 —...
Trane. The roof curb kit must be field assembled and numbers, as well as other pertinent unit data. A small installed according to the latest edition of the roof curb metal nameplate with the Model Number, Serial installation manual.
Stop unpacking the unit. All Unit Installations • Do not remove damaged material from receiving Startup MUST be performed by Trane, or an authorized location. agent of Trane, to VALIDATE this WARRANTY. • Take photos of the damage, if possible.
P P r r e e - - I I n n s s t t a a l l l l a a t t i i o o n n notification and true start date to Trane (or an agent of start-up and warranty of Trane®...
Dimensional Data Table 1. Unit Dimensions Refrigeration Foot- Pre-Evaporator Coil Overall Relief Option System Unit Function Outside Air print Filter Length Tons Performance Length (in.) (in.) Digit Digit Digit (in.) Type Type Type Type Digit 27 Type Digit 24 (in.) Retrieving data.
Page 14
D D i i m m e e n n s s i i o o n n a a l l D D a a t t a a Table 1. Unit Dimensions (continued) Refrigeration Foot- Pre-Evaporator Coil Overall Relief Option System Unit Function...
Page 15
D D i i m m e e n n s s i i o o n n a a l l D D a a t t a a Table 1. Unit Dimensions (continued) Refrigeration Foot- Pre-Evaporator Coil Overall Relief Option System Unit Function...
Page 16
D D i i m m e e n n s s i i o o n n a a l l D D a a t t a a Figure 1. 20 to 30 ton — front view (inches) 90.63 40.28 27.31...
Page 17
D D i i m m e e n n s s i i o o n n a a l l D D a a t t a a Figure 2. 20 to 30 ton — left view of sample configuration (inches) 220.88 38.85 87.66...
Page 18
D D i i m m e e n n s s i i o o n n a a l l D D a a t t a a Figure 3. 40 to 55 ton — front view (inches) 90.63 40.28 27.31...
Page 19
D D i i m m e e n n s s i i o o n n a a l l D D a a t t a a Figure 4. 40 to 55 ton — left view of sample configuration (inches) 81.59 87.66 79.33 300.88...
D D i i m m e e n n s s i i o o n n a a l l D D a a t t a a Figure 6. 60 to 75 ton — left view of sample configuration (inches) 320.73 38.63 81.59 87.90...
Page 21
D D i i m m e e n n s s i i o o n n a a l l D D a a t t a a Figure 8. Roof curb dimensions (inches) RETURN OPENING 4.01 OPENING TOP OF CURB 18.00 1.33...
Page 22
D D i i m m e e n n s s i i o o n n a a l l D D a a t t a a Table 2. Roof curb dimensional data (inches) Description RX, 20-30 T, PANEL 169.99 84.50 3.58 24.62 76.49 3.60...
Page 23
D D i i m m e e n n s s i i o o n n a a l l D D a a t t a a Figure 9. Base and pedestal 5.5" 3.4" GASKET BASE 4.3" 1.5"...
D D i i m m e e n n s s i i o o n n a a l l D D a a t t a a Electrical Entry Details Figure 10. Electrical connections (inches) ISO VIEW C CAB ISO VIEW A &...
. . A A d d j j u u s s t t a a s s n n e e c c e e s s s s a a r r y y f f o o r r e e v v e e n n u u n n i i t t l l i i f f t t . . Step-by-step curb assembly and installation instructions ship with each Trane accessory roof curb 1. To configure the unit Center-of-Gravity, utilize kit.
Page 28
I I n n s s t t a a l l l l a a t t i i o o n n Figure 15. Lug locations Tonnage Cartridge Filter Efficiency RA/RX Cabinet 20, 25, 30 40,50,55 High/Eflex High/Eflex 70,75 High/Eflex High/Eflex...
I I n n s s t t a a l l l l a a t t i i o o n n General Installation ☐ Complete the field wiring connections for the variable air volume controls as applicable. Requirements N N o o t t e e : : All field-installed wiring must comply with NEC The checklist below is a summary of the steps required...
I I n n s s t t a a l l l l a a t t i i o o n n control box, and the other end routed to a suitable percent Voltage Imbalance = sensing location within the controlled space. Voltage Supply where;...
I I n n s s t t a a l l l l a a t t i i o o n n Electrical Data MCA = 1.25 x (LOAD1 + LOAD2 + LOAD4) + (1.25 x LOAD3) Electrical Service Sizing For units using heaters equal to or greater than 50 kW: To correctly size electrical service wiring for a unit, find MCA = 1.25 x (LOAD1 + LOAD2 + LOAD4) + (1.0 x...
Page 32
I I n n s s t t a a l l l l a a t t i i o o n n Service Sizing Data Table 3. Compressor electrical service sizing data (20 to 75 tons) 200 V 230 V 460 V 575 V...
Page 33
I I n n s s t t a a l l l l a a t t i i o o n n Table 4. Condenser fan electrical service sizing data (20-75 ton) 200 V 230 V 460 V 575 V No.
Page 34
I I n n s s t t a a l l l l a a t t i i o o n n Table 6. Electrical service sizing data — Supply fan motors — 20 to 75 tons 200 V 230 V 460 V 575 V...
Page 35
I I n n s s t t a a l l l l a a t t i i o o n n Table 8. Electrical service sizing data (amps) - control power transformer heating and cooling modes - 20 to 75 tons Voltage Digit 2 Unit Nom Tons...
I I n n s s t t a a l l l l a a t t i i o o n n Main Unit Power Wiring W W A A R R N N I I N N G G P P r r o o p p e e r r F F i i e e l l d d W W i i r r i i n n g g a a n n d d G G r r o o u u n n d d i i n n g g Table 10, p.
Page 37
I I n n s s t t a a l l l l a a t t i i o o n n Figure 16. Typical field power wiring (20 to 75 ton) RE 200/230 ONLY: ADDITIONAL FIELD SUPPLIED DISCONNECT SWITCH FIELD SUPPLIED DISCONNECT SWITCH PITCH PITCH...
I I n n s s t t a a l l l l a a t t i i o o n n Supply Fans be removed, shown in Figure 17, p. 38. Gently spin each fan to verify there is no wheel-to-cone Remove Shipping Tie Down interference.
I I n n s s t t a a l l l l a a t t i i o o n n Figure 19. Supply fan cone overlap side of the O/A intake hood (for units without O/A intake, attach to panel at the return end of the unit).
I I n n s s t t a a l l l l a a t t i i o o n n Figure 21. Pressure sensing Figure 22. Condensate trap installation Top Port Connection 2' x 3/16" OD Tubing Factory Provided Post Outside Air...
I I n n s s t t a a l l l l a a t t i i o o n n Figure 24. Condensate drain locations for units with W W A A R R N N I I N N G G staggered indoor coils H H a a z z a a r r d d o o u u s s G G a a s s e e s s a a n n d d F F l l a a m m m m a a b b l l e e V V a a p p o o r r s s ! !
Page 42
I I n n s s t t a a l l l l a a t t i i o o n n Following the guidelines listed below will enhance both Failure to use a pressure regulating device will the installation and operation of the furnace.
I I n n s s t t a a l l l l a a t t i i o o n n Figure 26. Gas heat component dimensions Flue Vent Heat access (850 MBH shown) Gas pipe Combustion entry with inlet rain shield grommet CPVC Drain...
Page 44
I I n n s s t t a a l l l l a a t t i i o o n n Table 12. Sizing natural gas pipe mains and branches Gas Input (Cubic Feet/Hour) Gas SupplyPipe Run (ft) 1¼"...
Page 45
I I n n s s t t a a l l l l a a t t i i o o n n Table 15. Propane (LP) – high altitude rating reduction orifice chart Heater 0-2000' 3000' 4000' 5000' 6000' 7000' 8000'...
Page 46
I I n n s s t t a a l l l l a a t t i i o o n n Figure 27. Unit gas trains 250/350 MBh 2 stage/ Figure 28. Unit gas trains 250/350 MBh ultra modulating modulating and 500 MBh 2 stage/modulating Modulating valve...
I I n n s s t t a a l l l l a a t t i i o o n n Figure 29. Unit gas trains 500 MBh ultra modulating Figure 30. Unit gas trains 850/1200 MBh 4 stage/ modulating/ultra modulating Modulating valve One stage valve...
I I n n s s t t a a l l l l a a t t i i o o n n Gas Furnace Condensate Drain 3. Close the dampers by hand and tighten the actuator onto the jackshaft Units equipped with a gas furnace have a 3/4"...
Page 49
I I n n s s t t a a l l l l a a t t i i o o n n W W A A R R N N I I N N G G If the static pressure reading is greater than the pressure listed in Table 17, p.
Page 50
I I n n s s t t a a l l l l a a t t i i o o n n Figure 31. Outside air damper OUTSIDE AIR DAMPERS RETURN AIR DAMPERS BOTTOM VIEW OUTSIDE AIR DAMPERS BOTTOM VIEW RETURN AIR DAMPERS RT-SVX063E-EN...
Page 51
I I n n s s t t a a l l l l a a t t i i o o n n Table 16. Outside air damper travel adjustment Outside Air Damper Return Air Damper Crank Arm Hole Crank Arm Hole Configuration Configuration...
Page 52
I I n n s s t t a a l l l l a a t t i i o o n n Table 18. Outside air damper pressure drop — Traq™ ™ Traq™ ™ Outside Air Damper Position 20, 25 and 30 Ton 4000 0.07...
Page 53
I I n n s s t t a a l l l l a a t t i i o o n n Table 19. Return air pressure increase (continued) Return Air Damper Position 12000 0.00 0.10 0.22 0.33 14000 0.00 0.11...
Page 54
I I n n s s t t a a l l l l a a t t i i o o n n Table 20. Outside Air Pressure Drop (inches w.c.) – No Traq™ ™ (continued) No Traq™ ™ Outside Air Damper Position 100% 18000...
Page 55
I I n n s s t t a a l l l l a a t t i i o o n n Figure 32. Actuator stroke limit adjustment Figure 33. Actuator auto-scaling feature details Angle of Rotation Limiter Scale Shows % of Full Stroke Control Reversing Switch...
Startup the Unit Electrical Phasing Use the following in conjunction with the “Trane Startup Checklist,” p. 62, to ensure that the unit is W W A A R R N N I I N N G G properly installed and ready for operation. Be sure to...
Page 57
S S t t a a r r t t u u p p t t h h e e U U n n i i t t W W A A R R N N I I N N G G R R o o t t a a t t i i n n g g C C o o m m p p o o n n e e n n t t s s ! ! F F a a i i l l u u r r e e t t o o d d i i s s c c o o n n n n e e c c t t p p o o w w e e r r b b e e f f o o r r e e s s e e r r v v i i c c i i n n g g c c o o u u l l d d r r e e s s u u l l t t i i n n r r o o t t a a t t i i n n g g c c o o m m p p o o n n e e n n t t s s c c u u t t t t i i n n g g a a n n d d s s l l a a s s h h i i n n g g...
S S t t a a r r t t u u p p t t h h e e U U n n i i t t Direct-Drive Supply Fan Speed Table 23. RPM and Hz ranges for DDP supply fan speed adjustments (continued) Adjustment Fan Speed (RPM)
S S t t a a r r t t u u p p t t h h e e U U n n i i t t For relief fans, check the nameplate model number on carbon dioxide produced as a by-product of the fan to determine the K-factor, see table below.
S S t t a a r r t t u u p p t t h h e e U U n n i i t t of each burner's flame. Color should be blue for 2. Compare the measured oxygen level to the natural gas with a small amount of visible orange.
S S t t a a r r t t u u p p t t h h e e U U n n i i t t Final Unit Checkout Figure 35. One stage valve adjustment After completing all of the checkout and start-up procedures outlined in the previous sections (i.e., operating the unit in each of its Modes through all available stages of cooling and heating), perform these...
I I m m p p o o r r t t a a n n t t : : This checklist is not intended as a substitution for the contractor’s installation This checklist is intended to be a guide for the Trane instruction.
S S t t a a r r t t u u p p t t h h e e U U n n i i t t Table 26. Startup checklist (continued) Completed? Electric Heat (if applicable) Electric heat circuits have continuity Perform electric heat start up procedure Verify heating system matches name plate Gas Heat (if applicable)
Page 64
S S t t a a r r t t u u p p t t h h e e U U n n i i t t Figure 37. Dry bulb changeover map RT-SVX063E-EN...
Sequence of Operation N N O O T T I I C C E E subsequently manage the load using normal capacity control. A typical application is a data center. C C o o m m p p r r e e s s s s o o r r F F a a i i l l u u r r e e ! ! The unit configuration must have Rapid Restart F F a a i i l l u u r r e e t t o o f f o o l l l l o o w w i i n n s s t t r r u u c c t t i i o o n n b b e e l l o o w w c c o o u u l l d d r r e e s s u u l l t t i i n n configured as “Installed”...
Some sensors are field Occupied Occupied Any Number Occupied installed and may be wired or wireless. Field installed wired sensors are available from Trane and many other Occupied Unoccupied Zero Standby sources. In every case, the correct type of sensor must be used.
S S e e q q u u e e n n c c e e o o f f O O p p e e r r a a t t i i o o n n Daytime Warm Up fan operation continues to circulate air until the Morning Warm Up command is removed.
S S e e q q u u e e n n c c e e o o f f O O p p e e r r a a t t i i o o n n Table 30. Outdoor air damper minimum ventilation control Traq Outdoor Air Flow...
S S e e q q u u e e n n c c e e o o f f O O p p e e r r a a t t i i o o n n Multi Zone-VAV and Constant common when the unit is economizing and bringing in large quantities of outside air.
S S e e q q u u e e n n c c e e o o f f O O p p e e r r a a t t i i o o n n Discharge Air Reset The relationship of the calculated discharge air setpoint and discharge air temperature will drive heating and Discharge Air Reset is a method to save energy by...
S S e e q q u u e e n n c c e e o o f f O O p p e e r r a a t t i i o o n n space Cool Setpoint before the controller can sequence of operation in Occupied Heat and Occupied change to Cool.
S S e e q q u u e e n n c c e e o o f f O O p p e e r r a a t t i i o o n n C C o o o o l l E E c c o o n n o o m m i i z z e e r r + + D D X X — — Cool – Economizer + DX is M M i i n n i i m m u u m m O O N N T T i i m m e e —...
S S e e q q u u e e n n c c e e o o f f O O p p e e r r a a t t i i o o n n on unit type, efficiency, capacity stage and other limit On single circuit units, or two circuit units with one controls.
S S e e q q u u e e n n c c e e o o f f O O p p e e r r a a t t i i o o n n Balanced Compressor Staging or significant unit mode change occurs, The second are Inhibits which are typically temporary, self-correcting, The Balanced Staging function is a user-defined option...
S S e e q q u u e e n n c c e e o o f f O O p p e e r r a a t t i i o o n n This function prevents the addition of circuit capacity discharge saturated temperature.
S S e e q q u u e e n n c c e e o o f f O O p p e e r r a a t t i i o o n n Superheat High Limit Detection Modulating Coil Frost Limit Control applies to circuits with a variable speed compressor.
S S e e q q u u e e n n c c e e o o f f O O p p e e r r a a t t i i o o n n Configuration N N o o t t e e : : Under the most common scenario when both the EXV electronic controller and unit Electronic Expansion Valves are always installed on DX controller are power cycled, EXV Calibration...
S S e e q q u u e e n n c c e e o o f f O O p p e e r r a a t t i i o o n n Table 33. Economizer high-limit decision methods Outdoor Air Temperature <...
S S e e q q u u e e n n c c e e o o f f O O p p e e r r a a t t i i o o n n Reheat valve modulates to manage reheat capacity to unoccupied mode;...
Page 85
S S e e q q u u e e n n c c e e o o f f O O p p e e r r a a t t i i o o n n first. The Off and Running status of each manifold and for the air switch to correct itself, if not then lock out.
S S e e q q u u e e n n c c e e o o f f O O p p e e r r a a t t i i o o n n Overrides Table 37. External relief fan control points (continued) The controller normally provides heating, cooling and...
If both points are True (locked out) at the same time, Command and Cool Lockout Command are not locked- both will be honored. Trane Graphical Programming out; the control will limit capacity based on active (TGP2) can be used to control these points.
S S e e q q u u e e n n c c e e o o f f O O p p e e r r a a t t i i o o n n H H e e a a t t P P r r i i m m a a r r y y E E n n a a b b l l e e obstructed, the condensate level will begin to rise and the Condensate Overflow input will be activated.
Controls Constant Volume System of operating conditions that cause excessive motor temperature. These include rapid cycling, loss of Controls charge, abnormally high suction temperatures, excessive amperage, phase loss and low voltage Constant Volume Zone Panel (BAYSENS108*) CSHN Compressors This electronic sensor features four system switch PTC sensors are embedded in the motor windings of settings (Heat, Cool, Auto, and Off) and two fan settings each Scroll compressor.
Page 94
C C o o n n t t r r o o l l s s Figure 42. Compressor and condenser fan locations and names Refrigeration Systems: Refrigeration Systems: 20H, 20V, 25H, 25V, 30H, 30V 25S, 30S Circuit 1 Circuit 1 Condenser Condenser Fans &...
Page 95
C C o o n n t t r r o o l l s s Table 41. Compressor staging — 25S, 30S Table 47. Compressor staging — 40V Stage Comp 1A Comp 1B Comp 1C Comp Comp Comp Speed Speed pacity —...
Page 96
C C o o n n t t r r o o l l s s Table 52. Compressor staging — 75V Table 52. Compressor staging — 75V (continued) Comp Comp Comp Comp Spe- Spe- Comp Comp Comp Comp Spe- Spe- paci- paci-...
Please see notes below for all supply fan curves. For additional information or support, contact your local Trane sales office or Trane representative. 3000 RPM I I m m p p o o r r t t a a n n t t : : 2800 RPM 1.
Page 98
P P e e r r f f o o r r m m a a n n c c e e D D a a t t a a Figure 46. 20, 25 and 30 ton, 20.0 inch - 9 blade - 100% Figure 48.
Page 99
P P e e r r f f o o r r m m a a n n c c e e D D a a t t a a Figure 50. 40, 50 and 55 ton, 24.5 inch - 9 blade - 80% Figure 52.
Please see notes below for all supply fan curves. For additional information or support, contact your local 1980 RPM Trane sales office or Trane representative. 1900 RPM I I m m p p o o r r t t a a n n t t : : 1800 RPM 1.
Page 101
P P e e r r f f o o r r m m a a n n c c e e D D a a t t a a Figure 59. 50 and 55 ton, 12 hp relief fan, two-fan Figure 61.
P P e e r r f f o o r r m m a a n n c c e e D D a a t t a a Component Static Pressure Drops Table 53. Static pressure drops — relief dampers Relief Damper Pressure Drop Nominal Tons...
Page 103
P P e e r r f f o o r r m m a a n n c c e e D D a a t t a a RT-SVX063E-EN...
Page 104
P P e e r r f f o o r r m m a a n n c c e e D D a a t t a a RT-SVX063E-EN...
P P e e r r f f o o r r m m a a n n c c e e D D a a t t a a Refrigeration Table 55. Minimum outside air temperature Low Ambient Unit Minimum Outside Air Electronic Compressor Protection Temperature for Mechanical Cooling Module (CPM)
Service and Maintenance W W A A R R N N I I N N G G H H a a z z a a r r d d o o u u s s V V o o l l t t a a g g e e a a n n d d E E x x p p o o s s u u r r e e t t o o U U l l t t r r a a v v i i o o l l e e t t R R a a d d i i a a t t i i o o n n ! ! T T h h i i s s p p r r o o d d u u c c t t c c o o n n t t a a i i n n s s c c o o m m p p o o n n e e n n t t s s t t h h a a t t e e m m i i t t h h i i g g h h - - i i n n t t e e n n s s i i t t y y u u l l t t r r a a v v i i o o l l e e t t ( ( U U V V - - C C ) ) r r a a d d i i a a t t i i o o n n w w h h i i c c h h c c a a n n b b e e...
Page 107
S S e e r r v v i i c c e e a a n n d d M M a a i i n n t t e e n n a a n n c c e e Table 57.
Page 108
S S e e r r v v i i c c e e a a n n d d M M a a i i n n t t e e n n a a n n c c e e F F i i l l t t e e r r L L a a y y o o u u t t s s Table 58.
To clean refrigerant coils, use a soft brush and a sprayer. For evaporator and reheat coil cleaners, contact the local Trane Parts Center for appropriate detergents. 1. Remove enough panels from the unit to gain safe access to coils. RT-SVX063E-EN...
State and local laws. Refer to general pressure coil wand extension through the local service bulletin MSCU-SB-1 (latest edition). Trane Parts Center. Figure 63. Suction line filter installation 4. When cleaning evaporator and reheat coils, mix the detergent with water according to the manufacturer’s instructions.
Page 112
S S e e r r v v i i c c e e a a n n d d M M a a i i n n t t e e n n a a n n c c e e Refrigerant Evacuation and Charging evaporator coil, pumping refrigerant into the condenser coil to service the refrigerant system is no...
Page 113
S S e e r r v v i i c c e e a a n n d d M M a a i i n n t t e e n n a a n n c c e e Pressure Curves Figure 64.
Page 114
S S e e r r v v i i c c e e a a n n d d M M a a i i n n t t e e n n a a n n c c e e Figure 65.
Page 115
S S e e r r v v i i c c e e a a n n d d M M a a i i n n t t e e n n a a n n c c e e Figure 67.
Page 116
S S e e r r v v i i c c e e a a n n d d M M a a i i n n t t e e n n a a n n c c e e Figure 69.
Page 117
S S e e r r v v i i c c e e a a n n d d M M a a i i n n t t e e n n a a n n c c e e Figure 71.
Page 118
S S e e r r v v i i c c e e a a n n d d M M a a i i n n t t e e n n a a n n c c e e Figure 73.
Page 119
S S e e r r v v i i c c e e a a n n d d M M a a i i n n t t e e n n a a n n c c e e Figure 75.
Page 120
S S e e r r v v i i c c e e a a n n d d M M a a i i n n t t e e n n a a n n c c e e Figure 77.
Page 121
S S e e r r v v i i c c e e a a n n d d M M a a i i n n t t e e n n a a n n c c e e Figure 79.
Page 122
S S e e r r v v i i c c e e a a n n d d M M a a i i n n t t e e n n a a n n c c e e Figure 81.
Page 123
S S e e r r v v i i c c e e a a n n d d M M a a i i n n t t e e n n a a n n c c e e Figure 83.
Page 124
S S e e r r v v i i c c e e a a n n d d M M a a i i n n t t e e n n a a n n c c e e Figure 85.
Page 125
S S e e r r v v i i c c e e a a n n d d M M a a i i n n t t e e n n a a n n c c e e Figure 87.
Rotolock fitting is removed. The scroll compressor uses Trane OIL00079 (one quart Prior to reinstalling the oil equalizer line to each container) or OIL00080 (one gallon container) without compressor, replace the PTFE gasket on the oil substitution.
5. When the desired selection has been made, press compressor OK . Should replacing the VFD become necessary, the replacement is not configured with all of Trane's operating parameters. The VFD must be programmed before attempting to operate the unit. Precision Suction Restrictor...
Page 129
S S e e r r v v i i c c e e a a n n d d M M a a i i n n t t e e n n a a n n c c e e 2.
Page 130
S S e e r r v v i i c c e e a a n n d d M M a a i i n n t t e e n n a a n n c c e e Table 70.
Page 131
S S e e r r v v i i c c e e a a n n d d M M a a i i n n t t e e n n a a n n c c e e Table 70.
Page 132
S S e e r r v v i i c c e e a a n n d d M M a a i i n n t t e e n n a a n n c c e e Table 72.
S S e e r r v v i i c c e e a a n n d d M M a a i i n n t t e e n n a a n n c c e e Final Process Symbio 800 Replacement See Programming Guide (RT-SVP011*-EN) Symbio UI...
Page 135
S S e e r r v v i i c c e e a a n n d d M M a a i i n n t t e e n n a a n n c c e e RT-SVX063E-EN...
Wiring Diagrams Table 75. Wiring diagram matrix Description Number Power POWER SCHEMATIC, 20T-75T - AIRFLOW AND CONTROLS 1213-2567 1213-2568 POWER SCHEMATIC, 20T-75T - AIRFLOW AND CONTROLS W/ VFD BYPASS POWER SCHEMATIC, 40T-75T - REFRIGERATION 1213-2570 POWER SCHEMATIC, 40T-75T - REFRIGERATION WITH COMPRESSOR VFD 1213-2571 POWER SCHEMATIC, 40T-75T - REFRIGERATION WITH COND FAN VFD 1213-2572...
Page 137
W W i i r r i i n n g g D D i i a a g g r r a a m m s s Table 75. Wiring diagram matrix (continued) Description Number SCHEMATIC - ELECTRIC HEAT WITH SCR MODULATING - 90KW - 208V/240V, 190KW - 480V 1213-2847 SCHEMATIC - ELECTRIC HEAT WITH SCR MODULATING - 1200KW - 208V/240V 1213-2848...
PRODUCTS COVERED - This warranty* is extended by including implied warranties of merchantability and Trane Inc. and applies only to commercial equipment fitness for particular use. In no event shall the rated 20 Tons and larger and related accessories.
Page 140
For more information, please visit trane.com or tranetechnologies.com. Trane has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.